Maintenance-Object Repair Procedures
555-233-143
8-836
Issue 1 May 2002
Expansion Interface Neighbor Query Test (#237)
This test is nondestructive. The Expansion Interface Neighbor Query test is a
request to an EI circuit pack to determine whether it has established
communication with the EI or SNI circuit pack at the opposite end of the fiber.
For EI-to-EI fiber links, this test is run on both EI circuit pack endpoints of the fiber
link.
Table 8-324.
Test #237 Expansion Interface Neighbor Query Test
Error
Code
Test
Result
Description / Recommendation
1033
ABORT
The EI circuit pack does not have a fiber link administered to it. There is not
sufficient data to run test. Since the test fiber-link command was run, the
expansion interface should be administered on a fiber link, therefore this must
be a software problem.
2000
ABORT
Response to the test request was not received within the allowable time period.
1. Run the test board UUCSS test separately for each EI endpoint on this
fiber link and follow the procedures for this test in
.
2031
ABORT
The attempt to send the message to the EI circuit pack, asking it who it’s
neighbor is, was not successful.
1. Run the test board UUCSS test separately for each EI endpoint on this
fiber link and follow the procedures for this test in
.
2100
ABORT
System resources required to run this test are not available.
1. Run the test board UUCSS test separately for each EI endpoint on this
fiber link and follow the procedures in
‘‘EXP-INTF (Expansion Interface
.
2500
ABORT
Internal system error
1. Run the test board UUCSS test separately for each EI endpoint on this
fiber link and follow the procedures in
‘‘EXP-INTF (Expansion Interface
.
1033
FAIL
The EI circuit pack under test cannot make contact with opposite end EI or SNI
circuit pack.
1. Run the test board UUCSS test separately for each EI endpoint on this
fiber link and follow the procedures in
‘‘EXP-INTF (Expansion Interface
.
2027
FAIL
The EI circuit pack has contact with the opposite EI or SNI circuit pack, but it is
the incorrect EI or SNI circuit pack.
1. Run the test board UUCSS test separately for each EI endpoint on this
fiber link and follow the procedures in
‘‘EXP-INTF (Expansion Interface
.
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...