RDIG-STA (Remote Digital Station)
Issue 1 May 2002
8-1353
555-233-143
Table 8-548.
Test #17 Station (Digital) Audits Test
Error
Code
Test
Result
Description / Recommendation
1
ABORT
Switchhook audit timed out.
1. Make sure voice terminal is connected and repeat test.
2. If test fails, replace voice terminal and repeat test.
2
ABORT
ID request fails, health bit returned from voice terminal is bad.
1. Make sure voice terminal is connected and repeat test.
2. If test fails, replace voice terminal and repeat test.
3
ABORT
The EPF has detected an overcurrent condition.
1. Use test UUCSSpp long. If Test #11 passes, then the EPF condition was
cleared. Rerun the short test sequence. If Test #11 does not pass, follow
the repair procedures described for Test #11.
2. Look for Error Type 769 logged against RDIG-STA, and follow the
procedures in the associated footnote. If any additional problems are
found, rerun the test.
4
ABORT
Internal system error
1. Resolve any outstanding circuit pack maintenance problems.
2. Retry the command at 1-minute intervals up to 5 times.
5
ABORT
Ringer update aborted due to station being in ready-for-service or
out-of-service state.
6
ABORT
This port may have been busied out by a system technician.
1. Look in the Error Log for Error Type 18 (port busied out) for this port. If this
error is present, release the port using the release station command.
2. Make sure that the terminal is connected.
3. Retry the command at 1-minute intervals up to 5 times.
1000
ABORT
System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
1392
ABORT
This port is currently a TTI port and the test will not execute on it.
1. Verify that the port is a TTI port using either the display port command
(the display shows that the port is a TTI port) or the list config command
(the display shows a
t
for the port).
2. If either list config or display port indicate that the port is not a TTI port,
escalate the problem. If both commands indicate that the port is a TTI port,
the abort is correct, and no action is necessary.
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...