Installing the UPS
NOTE
Do not make unauthorized changes to the UPS or accessories; otherwise, damage
may occur to your equipment and void your warranty.
Figure 11 shows a typical installation only. See “UPS Rear Panels” on
page 29 for the rear panel of each model.
To install the UPS and optional EBMs:
1.
If installing an optional EBM, continue to Step 2; otherwise, skip to
Step 3.
2.
Plug the EBM cable(s) into the battery connector(s) as shown in
Figure 11. Up to four EBMs may be connected to the UPS.
ConnectUPS-X Web/SNMP Card
UPS Battery
Connector
Power Cord
EBM Cable
Output Receptacles
UPS
EBM
EBM
EBM Battery Connectors
Figure 11. Typical UPS Installation with Two EBMs
3.
Plug the equipment to be protected into the appropriate UPS output
receptacles (see page 47 for more information on load segments).
NOTE
DO NOT protect laser printers with the UPS because of the exceptionally high power
requirements of the heating elements.
4.
If an emergency power-off (disconnect) switch is required by local
codes, see the following section, “Remote Emergency Power-off
Installation,” to install the REPO switch before powering on the
UPS.