INSTALLATION
Avaya
t
S9RM UPS Site Preparation, Installation and Operator’s Manual
S
05147387 Rev C
28
NOTE
A separate contact must simultaneously cause UPS input AC power to be removed.
Pin 1
Pin 2
Figure 13. REPO Connector
4.
Connect the REPO connector to the REPO port on the UPS rear
panel.
5.
Verify that the externally-connected REPO switch is not activated to
enable power to the UPS output receptacles.
6.
Plug in the UPS and start the UPS by pressing the On
button.
7.
Activate the external REPO switch to test the REPO function.
8.
De-activate the external REPO switch and restart the UPS.
9.
If you are installing power management software, refer to the
ConnectUPS Web/SNMP Card Quick Start Instructions
and
ConnectUPS Web/SNMP Card User’s Guide
on the Software Suite
CD for configuration instructions.
For 2000 VA models with an Alarm Adapter, connect your computer
to the UPS communication port using the supplied communication
cable.