Avaya
t
S9RM UPS Site Preparation, Installation and Operator’s Manual
S
05147387 Rev C
37
Chapter 5
Configuration
This section describes:
S
Using Configuration mode to change the input voltage, site wiring
fault, and AC input alarm.
S
Using the ERM Configurator tool with a ConnectUPS-X Web/SNMP
Card
Configuration Mode
When the UPS is in Configuration mode, the bar graph indicators
represent the configuration options. Use the control buttons
(On
button and
button) to modify the UPS configuration. Figure 20
shows the LEDs and Table 1 explains the corresponding options.
NOTE
The UPS can be configured while in Battery mode. If the UPS transfers to battery
power while in Configuration mode, the UPS remains in Configuration mode and indicates
Battery mode on the front panel after exiting Configuration mode.
C A U T I O N
DO NOT press the Off
button while the UPS is in Configuration mode; pressing the
Off
button removes all power to your equipment immediately and the UPS enters
Standby mode.
To reconfigure the UPS default settings:
1.
Press and hold the On
button and the
button simultaneously
for approximately three seconds. The UPS transfers to
Configuration mode.
The LEDs flash briefly and then display the enabled options.