CONFIGURATION
Avaya
t
S9RM UPS Site Preparation, Installation and Operator’s Manual
S
05147387 Rev C
38
2.
Press the On
button to scroll through the options. Each time you
press the button, the UPS beeps. The LED for the selected option
indicates the current setting; flashing represents disabled options
(see Figure 20 and Table 1).
Scrolling past the last LED returns to the first configuration option.
If you press the On
button and nothing happens, the UPS is still in
Operation mode. Repeat Step 1 to enter Configuration mode, and
then perform Step 2.
3.
Press the
button ONCE to select the Voltage option or to toggle
the Site Wiring Fault Alarm or AC Input Failure Alarm on or off.
NOTE
The UPS automatically exits Configuration mode after two minutes.
4.
Press and hold the On
button and the
button simultaneously
for three seconds to exit Configuration mode at any time.
1
Press and hold the On and Test/Alarm Reset
buttons simultaneously for three seconds to
toggle between Configuration and Operation
modes.
&
4
Press the Test/Alarm Reset
button ONCE to select an
option.
3
Press the On button to
scroll to the next option.
2
On Button
Test/Alarm
Reset Button
Configuration Mode LEDs
Figure 20. Using Configuration Mode