Table 5. Weights and Dimensions
UPS
Extended Battery Module (EBM)
Dimensions
(WxDxH)
43.2 x 49.3 x 8.9 cm
17.0” x 19.4” x 3.5” (2U)
43.2 x 49.3 x 8.9 cm
17.0” x 19.4” x 3.5” (2U)
Weights
700–1000 VA: 15 kg (34 lb)
1500–2000 VA: 23 kg (50 lb)
29.5 kg (65 lb)
Table 6. Electrical Input
120V Models
230V Models
Nominal Voltage
120V default; 110, 120, 127V selectable*
230V default; 220, 230, 240V selectable*
Voltage Range
80–144V for 110, 120, 127V nominal
160–288V for 220, 230, 240V nominal
Nominal Frequency
45–65 Hz, 50/60 Hz auto-sensing
Noise Filtering
MOVs and line filter for normal and common mode noise
Connections
1000–1500 VA: 6-ft, 5-15P power cord
2000 VA: 6-ft, 5-20P power cord
10A, IEC 320-C14 input connector
* 208V nominal input voltage is available. Contact your Avaya service representative for assistance.
Table 7. Electrical Output
120V Models
230V Models
Power Levels (Rated at
Nominal Inputs)
1000 Model: 1000 VA, 700W
1500 Model: 1500 VA, 1050W
2000 Model (with 5-20R): 2000 VA, 1400W
700i Model: 700 VA, 490W
1000i Model: 1000 VA, 700W
1500i Model: 1500 VA, 1050W
Regulation
(Normal Mode)
Nominal output voltage ±3%
Regulation
(Battery Mode)
Nominal output voltage ±3%
Voltage Waveform
Normal mode: Sine wave; <5% THD with full PFC and nonlinear load
Output Receptacles
(6) 5-15R
2000 Model (with 5-20R) only: (2) 5-20R, (4) 5-15R
(6) IEC-320