SPECIFICATIONS
Avaya
t
S9RM UPS Site Preparation, Installation and Operator’s Manual
S
05147387 Rev C
57
Table 8. Environmental and Safety
120V Models
230V Models
Operating Temperature
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature
0°C to 25°C (32°F to 77°F)
Transit Temperature
-25°C to 55°C (-13°F to 131°F)
Relative Humidity
5–90% noncondensing
Operating Altitude
Up to 3,000 meters above sea level
Transit Altitude
Up to 10,000 meters above sea level
Heat Dissipation
(Recharge Mode up to
8 Hours)
1000 VA: 601 BTU/hr
1500 VA: 986 BTU/hr
2000 VA: 1201 BTU/hr
700 VA: 472 BTU/hr
1000 VA: 601 BTU/hr
1500 VA: 986 BTU/hr
Audible Noise
Less than 45 dBA Normal mode, typical load
Less than 50 dBA Battery mode
Surge Suppression
ANSI C62.41 Category B (formerly IEEE 587)
Safety Conformance
UL 1778, UL 497A;
CSA C22.2, No. 107.1, 107.2;
NOM-019-SCFI
UL 1778, UL 497A;
CSA C22.2, No. 107.1, 107.2;
EN 62040-1-1 and IEC 60950-1;
NOM-019-SCFI
Agency Markings
cULus, NOM
cULus, CE, NOM, NEMKO
EMC (Class B)
FCC Part 15, ICES-003, VCCI
EN 50091-2, FCC Part 15, ICES-003, VCCI
Table 9. Battery
UPS Configuration
700–1000 VA: (2) 12V, 9 Ah internal batteries
1500–2000 VA: (4) 12V, 9 Ah internal batteries
EBM Configuration
EBM 24: (8) 12V, 9 Ah
EBM 48: (8) 12V, 9 Ah
Type
Sealed, maintenance-free, valve-regulated, lead-acid
Charging
Internal battery: approximately 2 hours to 80% usable capacity
at nominal line voltage after full load discharge
External battery: no more than 10x discharge time to 90% usable capacity
at nominal line voltage after full load discharge
Monitoring
Advanced monitoring for earlier failure detection and warning