SPECIFICATIONS
Avaya
t
S9RM UPS Site Preparation, Installation and Operator’s Manual
S
05147387 Rev C
58
Table 10. Battery Runtimes (in Minutes)
700–1000 VA Models
Load
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
200 VA/140W
37
271
546
400 VA/280W
19
142
278
700 VA/490W
9
72
156
850 VA/595W*
6
59
124
1000 VA/700W*
5
48
104
* Runtimes do not apply for 700 VA models.
1500–2000 VA Models
Load
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
400 VA/280W
46
177
331
501
682
700 VA/490W
25
96
180
272
370
850 VA/595W
21
76
142
214
292
1000 VA/700W
16
61
115
174
237
1250 VA/875W
11
46
87
131
179
1500 VA/1050W
8
37
70
106
144
1800 VA/1260W**
6
30
57
85
116
2000 VA/1400W**
5
26
49
74
100
** Runtimes do not apply for 1500 VA models.
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.