7 Error codes and LCD messages
7.1 Error codes that are backward compatible to previous versions of
the SmartCal positioner
Err 3
(Error 3)
Low Input Pressure
Err 5
(Error 5)
Integrator Overflow – Actual position does not match set-point
Err 6
(Error 6)
Calibration Error - Positioner could not successfully perform
calibration
ALR
(Alert 3)
Valve position is not being maintained within the dead-band range.
The dead-band range (EDb) is set
from the configuration menu
during calibration (Section 4). The EDb must be set to other than
zero (0) to enable the Alert 3 message. Additionally, check the
following items:
Hall sensor connector and cable, especially if remote
Pressure supply stability
Actuator and tubing leaks
Magnet assembly in correct position and tight
Set-point
stability
Flow
turbulence
Sources of electromagnetic noise too close to the sensor or
to the positioner cables, like AC cables for motors, inverters
etc