Charger 6 / Charger 12
rel. 1.3c -E- english, page
17
of
22
L
LED indication system in the back panel.
DESCRIPTION
COLOUR
STATE
EVENT DESCRIPTION
From
Out 1
to
Out 12
yellow
on
Fault of output circuit breaker.
pulsating
Current is consumed from the particular output (the
indication is activated only before the outputs are
switched on).
off
Output switched on.
AUX
yellow
on
Fault of circuit breaker of additional outputs
off
Output switched on.
Relay indication system.
DESCRIPTION
STATE
EVENT DESCRIPTION
MAINS FAULT
on
Normal operation state at the mains present.
off
No mains or rectifier fault.
BATTERY FAULT
on
Correct battery operation.
off
High resistance of battery circuit or battery voltage below a preset
level (battery discharged).
GENERAL FAULT
on
No fault.
off
Fault within the power supply or external fault.
4.6
Maintenance
The device does not require any specific maintenance operations to be performed. During normal
operation of the unit care should be taken to maintain clean and tidy area around the power supply
unit.