24
Cyclades PM IPDU Installer/Administrator/User Guide
Arguments
If
<IPDU_ID>
follows
<IPDU#>
, or if the
<IPDU_ID>
parameter is typed twice, the latest entry
of the
<IPDU_ID>
parameter updates the ID string.
Examples
To set the ID of PM IPDU 1 R&D, enter:
To display the ID of PM IPDU 2, enter:
To rename an ID to “sammy,” using an existing ID “QA,” enter:
To display the IDs of all PM IPDUs in the daisy chain, enter:
interval
The interval command configures the time interval (in seconds) to turn on power for each outlet in
the system. This command is available to the admin user only.
Syntax
interval <outlet_number> <duration>
Arguments
NOTE:
When this value is set to 0.0, there is still an interval of approximately 0.1 seconds between outlets to
receive power.
<IPDU#>
IPDU number in a daisy chain
<IPDU_ID>
Identification string previously set by the id command
no argument
Displays the IDs of all PM IPDUs in the daisy chain
pm>
id 1 R&D
pm>
id 2
pm>
id QA sammy
pm>
id
<duration>
Sets the interval to turn on power to outlets. Valid intervals are
from 0 to 100. Default value is 0.5
<outlet_number>
Outlet number, such as “5”, outlet name such as “sunfire”, or group
of outlets such as “1, 3-5”
pm_install_admin_user.book Page 24 Tuesday, March 24, 2009 3:02 PM