Specifi cations

Mechanical

Size:

 17 x 8.272 x 1.719 in (horizontal), 

2.2 x 66 x 3.15 in (vertical)

Weight:

 7.3 lbs (horizontal without 

power cord), 14.8 lbs (vertical without 

power cord)

Environmental

Operating Temperature:

 50 to 122 F (10 

to 50 C)

Storage Temperature:

 -40 to 149 F (-40 

to 65 C) 

Network Connection

Number:

 1 

Type:

 10/100/1000 Ethernet

Accessories Included

Rackmount kit, toolless mounting 

hardware with vertical models and outlet 

retention clips

Standards

Approved Agency:

 

UL, FCC, cUL, CE, VCCI, C-Tick, CB

Warranty

Two Year

Ethernet

PM3000

Intelligent Power Distribution Unit

Features and Benefi ts

  

ƒ

Outlet level, phase level, and strip level current/voltage/power metering with threshold/alert capabilities*.  

 

Provides preemptive notifi cation of any impending overload issues before they occur, and simplifi es the  

 task of installing new equipment.  

*(Note- measurement reso/- %5)

  

ƒ

Capability 

to remotely switch outlets through onboard web interface, DSView 3 management software (Not  

 available on PM2000). 

Allows power to hung up IT equipment to be recycled, turned on or turned off  

 remotely for faster resolution time.
  

ƒ

On board web interface. 

Can be installed for direct access right out of the box or it can be confi gured  

 as part of a larger integrated solution using the DSView 3 software.
  

ƒ

IP and Serial interface options.

 Options to install by connecting directly to the network or save IP  

 connections by using the serial interface to connect directly to Avocent appliances already connected  
 to the network. 
  

ƒ

Daisy chaining. 

Saves the number of IP addresses or console / KVM ports that are required to  

 manage all power distribution needs.
  

ƒ

Integration with DSView 3 software. 

Single interface for management of IT equipment and IPDUs 

simplifi es mapping of outlets to servers and other equipment to reduce and minimize power cycling the 
wrong equipment.
  

ƒ

Integration with DSView 3 Power Manager. 

Track historical trends to measure and monitor IT power  

 consumption, capacity, and cost to understand what issues exist and to make more informed   
 decisions in the future.

 

  

ƒ

Electronic Overcurrent Protection. 

Electronic Overcurrent Protection is an added layer of protection  

 that is activated in the event of minor overloads. During such events, outlets are turned off fi rst  
 instead of the primary overcurrent protection (OCP) tripping.
  

ƒ

Sequential Startup. 

Protects integrity of all upstream electrical infrastructure by staggering the inrush  

 current draw of all plugged in devices.
  

ƒ

Internal temperature sensor and two optional external sensors. 

These sensors can measure    

 environmental factors at several different points within the rack. 

PM2000 
Part Numbers

PM3000 
Part Numbers Description

Ordering Details

North America

PM2001H-401

PM3001H-401

Horizontal 1-ph 24A 200-240V with L6-30, 3 C19 ports

PM2002H-401

PM3002H-401

Horizontal 3-ph 24A 200-240V with L15-30, 6 C19 ports

PM2005H-403

PM3005H-403

Horizontal 3-ph 40A 200-240V with Hubbell® CS8365C, 6 C19 ports

PM2005H-404

PM3005H-404

Horizontal 3-ph 48A 200-240V with IEC 309 60A, 6 C19 ports

PM2001V-401

PM3001V-401

Vertical 1-ph 24A 200-240V with L6-30, 21 C13 & 3 C19 ports

PM2002V-401

PM3002V-401

Vertical 3-ph 24A 200-240V with L15-30, 21 C13 & 3 C19 ports

PM2005V-403

PM3005V-403

Vertical 3-ph 40A 200-240V with Hubbell CS8365C, 21 C13 & 3 C19 ports

PM2005V-404

PM3005V-404

Vertical 3-ph 48A 200-240V with IEC 309 60A, 21 C13 & 3 C19 ports

International

PM2003H-401

PM3003H-401

Horizontal 1-ph 32A 220/230/240V with IEC 309 32A, 3 C19 ports

PM2004H-401

PM3004H-401

Horizontal 3-ph 16A 380/400/415V with IEC 309 16A, 6 C19 ports

PM2005H-406

PM3005H-406

Horizontal 3-ph 32A 380/400/415V with IEC 309 32A, 6 C19 ports

PM2003V-401

PM3003V-401

Vertical 1-ph 32A 220/230/240V with IEC 309 32A, 21 C13 & 3 C19 ports

PM2004V-401

PM3004V-401

Vertical 3-ph 16A 380/400/415V with IEC 309 16A, 21 C13 & 3 C19 ports

PM2005V-406

PM3005V-406

Vertical 3-ph 32A 380/400/415V with IEC 309 32A, 21 C13 & 3 C19 ports

External Sensors

PMHD-THS

Temperature, Humidity, Air Flow and dry contact combo sensor

PMHD-TS

Temperature only sensor

Note: PM2000 models include per outlet metering capabilities
         PM3000 models include per outlet metering and switching capabilities

          AMP values listed on the North American models are rated at 80% based on national electric codes.