1-  LAYOUT AND SETTINGS 

1.1   Optical board (QBASE)  

 

 

 

 

 
 
 

1.1.1  Terminal block MA. 

 

“+”  >>> NEGATIVE AT REST 
“–”  >>> POSITIVE AT REST 
“S”  >>> SYNCHRONISM 

Connect to the terminal block MA (clamps 

“+” & “–“) the end line resistor as shown in figure (

FIG.1

) . For the 

value keep to the instruction of the certified central unit. 

 

1.1.2  Connector CMA. 

Connect the connector of the visual device from the cover of the panel. 

 
 
 

1.2  Acoustic board (AVD FJ/CPD) 

 

 

 

 

 

 

 

 

 

 

 

 

1.2.1 JUMPERS FUNCTION  

To select the type of function desired keep to the instruction below. 

 

OPEN 

CLOSED 

SW4 

Swap of frequency Sound (

factory set up

Fixed Sound 

 

INSTALLATION MANUAL

 

 

® 

DOA V

 

 

– 

Fire alarm visual & sounding device for fire signalling

 

conform to regulation 

EN54-3

 

& EN54-23. 

CM3 

Output piezo 

SW4 

Type of suond 

selector 

 

CM4 

Connection board QBASE  

(factory connection) 

CM4 

CM5 

CM3 

SW4 

® 

– in 

+in 

 

R:  

R:  

Red

 wire

“+ 

OUT

” connected to “+ in” of the board AVD FJ/CPD (

factory connection

)

 

Black

 wire 

“ – 

OUT

” connected to  “– in” of the board AVD FJ/CPD (

factory connection

)

 

White wire connected to CM4 

of board AVD FJ/CPD  

(

factory connection

)

 

MA 

FIG 1 

Red

 wire 

“+ in” connected to “+ 

OUT

” of the board QBASE  (

factory connection

)

 

Black

 wire  

“– in” connected to “ – 

OUT

” of the board QBASE (

factory connection

)

 

OUT 