1- DESCRIPTION AND LAYOUT CARD

2- PROGRAMMING

The card has a dip switch SW1 that establish the following functions:

2.1 FREQUENCY MODULATION SELECTION (Selector 1 e 2)

Sel. 1

Sel. 2

FUNCTION

OFF (0)

OFF (0)

Fast modulation da 1300 a 2700Hz

(factory setting)

ON (I)

OFF (0)

Slow modulation da 1410 a 1780Hz

OFF (0)

ON (I)

Fixed sound 800Hz

ON (I)

ON (I)

Intermittent sound with 3 frequencies (800, 1600, 2800Hz)

2.2 OPTICAL SIGNALLING SELECTION (Selector

3)

Sel. 3

FUNCTION

OFF (0)

Flash is activated with fast blinking

(factory setting)

ON (I)

Flash is divided and is activated with alternately blinking

3- CONNECTION AND ACTIVATION

The activation of the fire alarm sounding device is done by applying the "+ power" and "- power" to the corresponding
terminals

“+ IN”

and

“― IN”

,

while in the rest condition is applied to terminals reverse voltage.

When the central unit turns in alarm condition it will reverse the inverting output causing the activation of the fire alarm
sounding device.In the cutting cable condition the central unit will recognize the changing of the line (will not recognize
the  value  of  end  line  resistance  ”R”  indicates  at  point  1

"DESCRIPTION  AND  LAYOUT  CARD")and  turns  in  alarm

condition but don’t turn the fire alarm sounding device

in alarm condition too.

ATTENTION:
At the power on supply (start up) ,the siren active the flash with the left side and then the right side.

NOTE:

In alarm condition the temporization is infinite.

4- MAINTENANCE

To ensure proper operation over time is recommended once a year activation sound of a fire alarm device and a check
of the correct fixing to the wall

Power terminal

block

CM1

Flash connection

SW1

Programming selector:

Position 0 selector

OFF

Position I selector

ON

CM1

1 3

ON

OFF

TECHNICAL MANUAL

®

STAR F24/CPD

– Outdoor fire alarm sounding device EN 54-3 complies

®

Horn terminal

block

– IN

>> Positive power in st-by

+ IN

>> >> Negative power in st-by

SW1

R:

Connect the end of line resistor as

shown in FIG. For the value should be as
described in the instructions of the Central
Fire certified

.

+ IN

– IN