General Alarm Configuration
In “Degrees Within Threshold Before Alarm Is Cleared,” you may leave the default, 1, or enter a
value between 0.1 and 25.5.
You may use this feature to adjust how close your digital temperature sensor readings must get to
a high or low threshold before their alarms clear. For example, with the default setting here of 1º
and a high threshold of 80º, your temperature sensor will alarm when the temperature rises above
80º and clear when it falls below 79º; likewise, with a low threshold of 60º, the sensor will alarm
when the temperature falls below 60º and clear when it rises above 61º.
Internal Sensor Alarm Configuration (Internal Temperature & Humidity Sensor)
You may configure alert thresholds for the Internal Temperature & Humidity Sensor in the
“Internal Sensor Alarm Configuration” field. The temperature range is -40° to 185° F (-40° to
85° C), and the humidity range is 5% to 95 %RH.
1.
In “Sensor Label,” you may leave the default label, “Internal Sensor,” or rename it to
something more descriptive, such as “Int Temp & Hum.”
2.
The “Alarm On” field is set at the defaults of “Temperature (F)” and “Humidity (%RH).”
Notice the “Alarm Profile” drop-down menu next to each sensor.
If you have a Light Tower or Relay Switch Sensor connected to
your Room Alert via a Light Tower & Relay Adapter, you may
configure Alarm Profiles. Please refer to the
Alarm Options
section in this manual for further information.
NOTE