Room Alert 32E
36
AVTECH Software, Inc.
Relay 1 – 2 Action Configuration
Here you may set the devices connected through the built-in relay output ports to turn on or off
in response to your Room Alert 32E rebooting or its sensors going in and out of alarm state.
In this example, we’ll configure Relay 1.
1.
In “Sensor Label,” you may leave the default, “Relay 1,” or enter something more
descriptive, such as “Server Rm AC.”
2.
In the “On Boot” column, you may select what the relay output does in response to the
Room Alert 12E rebooting. The default is “Off.”
3.
In the “Profile 1–5” columns, you may create up to 3 different sets of on/off actions to
associate with sensors when they go in and out of an alarm state. In this example, we’ve
configured Profile 1 and left Profiles 2 through 5 at the default of “None.”
Associate Alarm Profiles With Sensors
Each sensor is set at “Profile 1” by default: the Light Tower, built-in LTA Relay, Relay Switch
Sensor and built-in Relay Output execute Profile 1 when that sensor goes into an alarm state.
Once you have configured at least 1 more profile, you may associate it with a sensor. When that
sensor goes into an alarm state, the features of those devices react by turning on or off.
In our example, we will associate Profile 1 with our external Digital Temperature Sensor and
Profile 2 with our external Room Entry sensor.
1.
Navigate to
Settings
Sensors
.
2.
Find your sensor’s interface and choose the profile you’ve configured from the drop-
down list in “Use Alarm Profile.” Note that the default for all sensors is Profile 1.