Configure Your Digital Temperature Sensor

Configure Your Digital Temperature Sensor

Use Room Alert’s Built-In Web Interface

Navigate to 

Settings

 

 

Sensors

 in the web interface of your Room Alert. The options 

you see below will vary depending on the model.

1.  Scroll to your external digital sensor(s), the total number of which will vary depending 

on the Room Alert model.

2.  Find the digital sensor interface that matches the port you connected your Digital 

Temperature Sensor to. For example, if you used the first digital port on your Room 

Alert, look for 

Sensor 1 Alarm Configuration

; if you used the second, look for 

Sensor 

2 Alarm Configuration

, and so on. Notice that your Room Alert monitor automatically 

detects the type of digital sensor and displays it in 

Sensor Type

.

3.  In 

Sensor X Label

, you may leave the default, “Ext Sensor X,” or enter something more 

descriptive of up to 15 characters. You may use the following characters in sensor 

labels: letters, numbers, spaces, hyphens (-), underscores (_) and periods (.). 

4. 

Alarm On

 automatically populates with the default temperature scale. Please refer to 

your Room Alert 

User’s Guide & Reference Manual

 to change it.

5.  In 

High

 and 

Low

, you may leave the default, 0—which means no alarm is configured—

or enter values for high and low thresholds. Your Room Alert generates alerts based on 

those thresholds.

6.  In 

Adjust

, you may leave the default, 0, or enter a value to adjust the temperature 

reading if it differs from a known value at that location.

7.  In 

Use Alarm Profile

, which controls light towers and relays on your Room Alert, you 

may leave the default, 

Profile 1

, or choose another profile from the drop-down menu.