background image

CM-1115(20)-RT-AR User Manual

 

Page 26

 

 

 

 

VIII.      DxP Protocol 

(continued)

 

 

 

 

 

Descriptors (con’t) 

 

 

eCmnd_keepAlive 

 

typedef enum{ 

eKeepAlive_null; 

} eKeepAlive; 

 

Command

 

Description

 

Server Response

 

eKeepAlive_null 

This is the only valid descriptor that the keep alive 
command supports. It is defined as null, as it carries 
no payload. 

0 → Successful 

1 → Error 

Summary of Contents for CM-1115-RT-AR

Page 1: ...Customer Service 800 645 9721 Technical Support 800 645 9721 Fax 919 269 0454 www surgex com Hardware Installation Guide Axess Ready Compact Mount Surge Eliminator Power Conditioner CM 1115 20 RT AR...

Page 2: ...TIONS 5 III LED INDICATORS 6 IV REMOTE CONTROL CONNECTIONS 6 CONTROL INPUTS 6 EXTERNAL LED CONNECTIONS 7 AUXILIARY RELAY CONTACTS 7 V INITIAL SET UP 8 DEVICE MANAGEMENT UTILITY DMU 8 SETTING THE IP AD...

Page 3: ...PROMPTS 18 CONTROL COMMANDS 18 DEVICE COMMANDS 18 NETWORK COMMANDS 19 AUTOPING COMMANDS 20 USER COMMANDS 20 EVENT COMMANDS 21 VIII DxP PROTOCOL 22 OVERVIEW 22 HELLO HANDSHAKE 22 DXP PACKET 23 COMMAND...

Page 4: ...energy by powering down equipment when not in use Telnet access uses the Command Line Interface CLI structure and syntax to completely configure and control the CM 1115 20 RT AR This Axess Ready AR d...

Page 5: ...are Input power plug NEMA 5 15 or 5 20 depending on model Network connection RJ 45 Circuit breaker 15A or 20A depending on model Output receptacles Reset button Axess On LED Power LED Over Under Volta...

Page 6: ...ct The base unit input power cord length is 9 Ethernet Connection The RJ45 connector for 10 100 Ethernet is situated on the front panel above the LED indicator array The default IP Address is 192 168...

Page 7: ...rminal block to make connections and after you have made the connections to the terminal block plug it back into the connector on the rear of the unit Never solder tin wires before inserting into a te...

Page 8: ...V output a series resistor is required For example many LEDs work well with 10mA of current so a 1K resistor is usually a good choice If more than one LED is required then use a separate series resist...

Page 9: ...g up the AR The utility will only work with ARs on the same local subnet as the PC Device Discover Automatically discover all ARs on the local network The DMU will display the location name of the AR...

Page 10: ...work connections Exit Exits the DMU program Help Online Help Opens a web browser to online help resources About Displays DMU version information Setting the IP Address ARs are configured with a factor...

Page 11: ...s from a DHCP server A DHCP server will automatically assign an IP address dynamic address as well as the Subnet Mask and Gateway To determine what IP address has been automatically assigned by the DH...

Page 12: ...the AC output will return to its last known state prior to the outage Press Cycle Power to temporarily change the state of the AC output for a specified cycle time factory default is 10 seconds The c...

Page 13: ...power cycle 1 999 seconds This is the amount of time the outlet will temporarily be On or Off depending on the initial outlet state Upgrade Enable Enables the ability to upgrade the firmware of the A...

Page 14: ...decimal format This field will be automatically set if using DHCP Gateway Enter the Gateway in dotted decimal format This field will be automatically set if using DHCP HTTP Port Specify the port the w...

Page 15: ...s Service monitor AR is installed with the device to be rebooted but pings a remote host to test the communication channel Ideal for DSL Cable Modem verification AR monitors a network device and power...

Page 16: ...net or DxP Power Off Follow Upon triggering AR will power off When the ping response returns AR will power on Power Cycle Upon triggering AR will cycle the power AR will then wait for Ping Frequency x...

Page 17: ...ntp org Enable Checking the Enable box enables the time scheduling feature Time Server Enter the IP address of the Network Time Server to be used Time Zone Specifies the local time zone relative to G...

Page 18: ...sword allows control of the AC receptacle state but provides no access to Setup functions The Administrator password allows full control and setup of the AR Passwords may be up to 20 characters long a...

Page 19: ...r changes have been made that require a reboot This prompt will remain active until the AR has been rebooted Control Commands Command Description Admin Fact Def get outlet Returns the current status o...

Page 20: ...t Mask Yes 255 255 255 0 set gateway dotted decimal Sets the Gateway address Yes 192 168 1 1 set http port 0 65535 Sets the port that the internal Web server listens for incoming connections on When s...

Page 21: ...requency 1 999 Sets the frequency how often the ping is sent for AutoPing 1 or 2 in seconds Yes 10 set autoping 1 2 failcount 1 999 Sets the number of consecutive failures the AutoPings must detect be...

Page 22: ...e server dotted decimal Sets the IP address of a Network Time Server Yes 64 90 182 55 set time enable yes no Enables or disables the use of a time server and scheduled t Yes No set event 1 8 date mm d...

Page 23: ...bled all messages must be encrypted with the AES Passphrase set in the device After the Hello a Command and Response sequence follows Any number of Command Response sequences are permitted after Hello...

Page 24: ...f a user on the ipIO that is being accessed password Reserved for future use It will contain the password of the user above desc Command descriptor that describes the individual command within a comma...

Page 25: ...and is used to set programmable variables on the server 2 eCmnd_get This command is used to get programmable variables from the server 3 eCmnd_io This command is used to monitor and control the I O on...

Page 26: ...sed to change the status of an individual relay It carries the TChangeRelay payload see the Payloads subsection for details 0 Successful 1 Error eIO_changeRelays This command is used to set all of the...

Page 27: ...Descriptors con t eCmnd_keepAlive typedef enum eKeepAlive_null eKeepAlive Command Description Server Response eKeepAlive_null This is the only valid descriptor that the keep alive command supports It...

Page 28: ...ned char relayStates 32 TChangeRelays Where relayStates is an array of relay states as defined below define NO_CHANGE 0 define ENERGIZE 1 define RELAX 2 This payload is supported by devices that suppo...

Page 29: ...Enable box on the Device web page 3 Run the DMU If the AR you would like to upgrade is not visible in the list box either Select Device Discover from the menu to locate the ARs on the local network S...

Page 30: ...el performs 3 functions as detailed below Action Result Momentary Soft Reset Will not affect outlet state 5 Second Push Reset to Factory Defaults Hold until the System On LED is blinking then Hold whi...

Page 31: ...age Shutdown 90 Volts resume at 100 Volts Maximum Load Inrush Energy 1000 Joules total during power up EMI RFI Filter Normal Mode 50 load 40 dB 100 kHz 50 dB 300 kHz 50 dB 3 MHz 50 dB 30 MHz Common Mo...