Remarks
Storage recommendation
For long-term storage (more than 3 months), the battery cells should be stored in a temperature
range of 5~45
℃
, relative humidity <65% and in no corrosive gas environment.
The battery modules should be shelfed in a temperature range of 5~45
℃
, in a dry, clean and
well ventilated environment. Before storing, the batteries should be charged to 50~55% SoC;
It is recommended to activate (discharge and charge) the battery every 3 months, and the
longest discharge and charge interval shall not exceed 6 months.
Caution: If the above instructions for long term storing the battery are not followed, the cycle life
will have a relative heavy reduction.
Capacity expansion
A new battery module can be added onto an existing system at any time. Please make sure the
existing system is fully charged before adding a new module. In a serial connected system, the
new module has a higher SOH, but it will follow the system
’s
worst module to perform.
7.
Shipment
Battery modules will be pre-charged to 100%SOC or according to customer requirement before
shipment. The remaining capacity of battery cell after shipment and before charge, is determined
by the storage time and condition.
1. The battery modules meet the UN38.3 certificate standard.
2. In particular, special rules for the carriage of goods on the road and the current dangerous
goods law, specifically ADR (European Convention on the International Carriage of Dangerous
Goods by Road), as amended, must be observed.
Any further questions, please contact Axitec: energy@axitecsolar.com