14
03
AC input voltage range
Appliances (Default)
If selected, acceptable AC input
voltage range will be within
90-280VAC.
UPS
If selected, acceptable AC input
voltage range will be within
170-280VAC.
04
Power saving mode
enable/disable
Saving mode disable
(default)
If disabled, no matter connected
load
is low or high, the on/off
status of
inverter output will not be
effected.
Saving mode enable
If enabled, the output of inverter
will
be off when connected load is
pretty
low or not detected.
05
Battery type
AGM (Default)
Flooded
User-Defined
If “User-Defined” is selected,
battery charge voltage and low DC
cut-off voltage can be set up in
program 26, 27 and 29.
Pylontech battery
If selected, programs of 02, 26, 27
and 29 will be automatically set
up. No need for further setting.
WECO battery
If selected, programs of 02, 12,
26, 27 and 29 will be
auto-configured per battery
supplier recommended. No need
for further adjustment.