2-5
2-2. SVP Installation procedure
The Smart Valve Positioner 100 Series can be attached onto a variety of actuators. Example
actuator mountings are shown below. Please refer to the installation instructions that were
included with your actuator mounting kit.
Example1: How to mount the SVP onto a linear motion actuator.
Fasten the mounting plate onto the SVP securely, using the 2 provided hexagon head bolts
(M8) and spring washers.
Assemble the connector pin assembly to the pointer with the hexagon socket head flange
bolt.
Set the valve travel to 50%.
Fasten the assembled SVP to the actuator using the bolts and washers provided while
guiding the 1/4 inch (6 mm) feedback pin through the slot on the feedback arm above the
spring with the feedback lever set to be horizontal.
Make sure that the feedback lever and pin form a right angle as shown below.
Hexagon head bolt
Spring washer
Mounting plate
Feedback lever
Spring
Pin
SVP
Yoke connection
Hexagon socket head flange bolt
Connector pin assembly
Pointer
Fig. 2-4.