5-8
5-7. Table of default internal data values
Item
Default value
Tag number
XXXXXXXX
Output format
ANALOG XMTR
Burnout direction
DOWN SCALE
Actuator operation
REVERSE
Positioner operation
DIRECT
Valve operation
DIRECT
Actuator size
PARAM 1
Hysteresis
HEAVY
PID parameters
(parameter 0)
P
1.200
I
4.000
D
0.5000
GE
+/-0.000%
GP
0.7000
GI
4.000
GD
0.5000
Flow characteristics
LINEAR
User defined flow characteristics data
(Pressure balance type adjustment valve
(ADVB/ADVM) linear characteristics data)
Valve fully closed value (LRV)
4.000mA
Valve fully open value (URV)
20.00mA
Forced fully closed input value
0.5000%IIN
Forced fully open input value
109.00%IIN
Digital output
settings
Output signal mode
Single Range
Amount of data mode DE-4Byte
Failsafe mode
F/S=B/O Hi