4-15
4-4-7. Travel Cutoff
Sets the input signal values (%) that force the valve fully open and fully closed. The valve will
be fully closed at input values less than the forced fully closed value, and will be fully open at
input values greater than the forced fully open value. The input signal values (%) for the valve
forced fully open and fully closed are set independently. An overview of the input/output
characteristics when forced fully closed/open values have been set is shown below.
Fig. 4-4. Forced Fully Open/Closed Settings
Note) Set these parameters such that the forced fully open setting (Travel Cutoff High) is greater
than the forced fully closed setting (Travel Cutoff Low).
If a span adjustment is performed after auto-setup has been executed, the forced fully
open setting will be 1 % less than the overstroke percentage.
The forced fully open and forced fully closed settings have a hysteresis difference of 0.1 %
As a result of configuring the forced fully closed setting, the control valve can become fully
closed when the input signal drops to the preset value or lower, so set the output limiter
(Lo) on the host to −1 % or higher.
Travel Cutoff Low configuration procedure
step
Procedure
1
Select [Device] >> [Setup] >> [Travel Cutoff] >> [Travel Cutoff Low].
2
Specify the input signal value at which to force the valve fully closed.
3
Send the modified setting to the device using the transmission button.
Travel Cutoff High configuration procedure
step
Procedure
1
Select [Device] >> [Setup] >> [Travel Cutoff] >> [Travel Cutoff High].
2
Specify the input signal value at which to force the valve fully open.
3
Send the modified setting to the device using the transmission button.
Summary of Contents for 100 Series
Page 1: ...CM2 AVP100 2001 Smart Valve Positioner 100 Series Model AVP100 102 User s Manual ...
Page 12: ...1 4 ...
Page 28: ...2 16 ...
Page 36: ...4 4 4 2 1 Menu Tree ...
Page 75: ......
Page 78: ......
Page 80: ......