4-14
(b) Reverse action type
Step
Procedure
1
Disconnect the air piping and detach other external items from the actuator.
2
Remove the stem connector, pointer and lock nut.
3
Remove the clamping-bolts (except the pair of eyebolts) of the diaphragm
case.
4
Loosen evenly and alternately the pair of eyebolts. (The initial setting of the
springs is done by these eyebolts.)
5
Remove the diaphragm case. Remove the springs.
6
Pull the actuator rod upward together with the diaphragm.
Fig. 4-10. Actuator Model HA2R or
HA3R
Fig. 4-11. Actuator Model HA4R
Eye
bolt
Hex bolt
Eye bolt
Diaphragm
case (top)
Hex nut
Lock
nut
Lock
nut
Hex nut
Hex bolt
Diaphragm
case (bottom)
Pointer
Pointer
Yoke
Yoke
Spring
Spring
Stem
connector
Stem
connector
Diaphragm
case (top)
Diaphragm
case (top)
Diaphragm
case (bottom)
Actuator
rod
Actuator
rod