75
■
Bar graph base position
• This sets the base position for bar graphs on the bar graph screen at a value from 0 to 100. At a
setting of 0, bars start on the left side (or the bottom) of the screen. At a setting of 100, bars start
on the right side (or the top).
Setting:
0 Setting:
50
Setting:
100
■
Zone usage
• The display range of the measured/calculated data is called the zone. When the zone is set to ON,
the display range can be divided into zones. For more details, see the next page.
■
Numeric display frame count
•
Set the number of divisions of the numeric display frame from one of
1/2/3/4/6/8/9/10/12/24/36/48/56.
■
Max/min display (numeric display)
•
Select one of “With or “Without”. When “With” is selected, the minimum and maximum values of
that channel data are displayed in the numeric display screen. Note, however, that these values
are not displayed when the numeric display frame count above is set to 24 or higher.
■
Screen auto switching period
• Determines how often the display is automatically switched, if “Auto switching” has been set to ON
with the DISP menu.
■
Data value updating interval
• Determines how often the measured data displayed on the screen is updated.
0.5 seconds, 1 second
■
Dual trend synchronization
• If a file with past data is opened as a dual trend when the function above is ON, the data will scroll
at the same rate as that of the real-time trend. When scrolling reaches the end of the file, if there
is a consecutive file, it will open automatically and scrolling through it will begin.