6
Chapter 2. Installation, Wiring
CAUTION
The ignition transformer ground must be directly connected to the burner itself or to metal
that is electrically connected to the burner.
Check that the wiring is correct before use. Incorrect wiring may cause damage or faulty
operation.
If the wiring from this device exceeds the recommended length, prevent malfunction due
to the effects of external noise by running wires from the control panel to the case through
a conduit, keeping power lines and input lines apart from each other, and other measures.
Check the operation of the system after installation.
Use non-voltage contacts for connections to the input terminals of this device (19 through 24).
This device does not start operation until about 8 seconds after power-on.
When discarding of this device, dispose of it as industrial waste, following local regulations.
Use a surge protector or similar device if there is a risk of power surges caused by lightning.
Do not configure a circuit that turns off the interlock input (terminals 22–19 or 22–20) using
the alarm output contacts (terminals 9–10). With such a circuit, if a false flame, UV alarm,
ignition failure, or flame failure occurs, the interlock alarm (E1) may be displayed.
When the control load wiring is grounded, an alarm occurs.
Use the contact reset (terminal 24) input in isolation. Do not share the terminal with other
AUR455 devices.
Do not share the output common (terminals 4 & 5) and the input common (terminals 19 & 20)
with other AUR455 devices.
Do not provide instrumentation to stop the power to the device as soon as the alarm operates.
When the power to this device is turned on again, an alarm may be activated (E908).
To prevent malfunction caused by the effect of external noise, in operations other than trial
operation, maintenance, or troubleshooting, do not keep the loader cable connected during
the operation.
Take countermeasures based on the instruction manual for that device if there is a device such
as an inverter nearby that generates strong electrical noise.
Firmly tighten the terminal screws to the torque listed in the specifications.