Chapter 5: Maintenance and Troubleshooting
5-7
■
Procedure for switching from automatic to manual operation
The procedure for switching from automatic operation to manual operation is shown
below.
Step
Procedure
1 Open the A/M switch cover plate by manually rotating it clockwise 180°. (The cover plate
can be made to rotate easily by pressing on the upper left of the cover plate at the same
time.)
2 Rotate the A/M switch one turn in the counterclockwise direction (the MAN direction)
using a flat-blade screwdriver. (Confirm the change using an output air pressure gauge.)
■
Procedure for switching from manual to automatic operation
The procedure for switching from manual operation to automatic operation is shown
below.
Step
Procedure
1 Rotate the A/M switch one turn in the clockwise direction (the AUTO direction) using a
flat-blade screwdriver. (Confirm the change using an output air pressure gauge.)
2 Manually rotate the A/M switch cover plate counterclockwise 180° until it stops with a
clicking sound.
Caution
•
Do not loosen the A/M switch cover plate screw.
•
Do not rotate the A/M switch too far in the counterclockwise direction, as doing so
will cause the O-ring to detach, resulting in air leakage.
Summary of Contents for AVP200
Page 30: ......
Page 66: ...2 28...
Page 80: ...4 4 Menu Tree...
Page 120: ...5 16...
Page 128: ...6 8 For models those date of manufacture are before September 2017...
Page 130: ...6 10 For models those date of manufacture are before September 2017...
Page 132: ...6 12 For models those date of manufacture are before September 2017...
Page 136: ...6 16 For models those date of manufacture are after October 2017...
Page 138: ...6 18 For models those date of manufacture are after October 2017...
Page 184: ...Appendix A Specifications A 25...
Page 185: ......
Page 188: ......
Page 190: ......