A-6
Item
Specification
Approvals
Combination of
NEPSI Flameproof
and Intrinsically safe
When used as NEPSI Flameproof, it complies NEPSI Flameproof approval
as above.
When used as NEPSI Intrinsically safe, it complies NEPSI Intrinsically safe
approval as above.
IECEx Flameproof
Ex db IIC T6 Gb
IEC IP66
Flameproof cable gland must be Ex db IIC approved.
Note: IP66 waterproof and dust-proof performance can be assured by installing
an appropriate cable gland.
INMETRO
Flameproof
Ex db IIC T6 Gb
Flameproof cable gland must be Ex db IIC approved.
Note: IP66 waterproof and dust-proof performance can be assured by installing
an appropriate cable gland.
EAC Flameproof
1 Ex d IIC T6 X
IEC IP66
Flameproof cable gland must be Ex d IIC approved.
Note: IP66 waterproof and dust-proof performance can be assured by installing
an appropriate cable gland.
EAC Intrinsically safe 0 Ex ia IIC T4 X
IEC IP66
Input circuit (terminals ±IIN)
Model AVP300/301: Ui=30 V, Ii=100 mA, Pi=1 W, Ci=1 nF, Li=0.2 mH
Model AVP302: Ui=30 V, Ii=100 mA, Pi=1 W, Ci=26 nF, Li=0.2 mH
Output circuit (terminals ±IOUT)
Model AVP301: Ui=30 V, Ii=100 mA, Pi=1 W, Ci=3 nF, Li=0.2 mH
Note: IP66 waterproof and dust-proof performance can be assured by installing
an appropriate cable gland.
CNS Flameproof
Ex d IIC T6 Gb X
IEC IP66
Flameproof cable gland must be Ex d IIC approved.
Note: IP66 waterproof and dust-proof performance can be assured by installing
an appropriate cable gland.
CE Marking
EN61326-1:2013 (EMC), EN50581:2012 (RoHS)
Configuration tools
Field Communication Software CommStaff Model CFS100
* This applies only to positioners with travel transmission (model AVP301). In this case, a power supply circuit for travel transmission is required.
Conditions of supply air (JIS C1805-1 (2001))
Item
Specification
Particles
Maximum diameter 3 μmm
Oil mist
Less than 1 ppm at mass
Humidity of the air supply
The dew point should be at least 10°C lower than the temperature of this device.
To meet the above specifications for instrument air, install the air purification devices listed below properly in the specified installation location.
Examples of air purification devices
Installation
Air purification device
SMC corporation
CKD corporation
Compressor outlet or main line Line filter
AFF series
AF series
Mist separator
AM series
Terminal device
Air combination
AW30
M3000S type
Summary of Contents for AVP200
Page 30: ......
Page 66: ...2 28...
Page 80: ...4 4 Menu Tree...
Page 120: ...5 16...
Page 128: ...6 8 For models those date of manufacture are before September 2017...
Page 130: ...6 10 For models those date of manufacture are before September 2017...
Page 132: ...6 12 For models those date of manufacture are before September 2017...
Page 136: ...6 16 For models those date of manufacture are after October 2017...
Page 138: ...6 18 For models those date of manufacture are after October 2017...
Page 184: ...Appendix A Specifications A 25...
Page 185: ......
Page 188: ......
Page 190: ......