2-19
Chapter 2: Installation
■
Adjusting length of remote cable
Step
Procedure
1
Remove the remote cable from the terminal box, and then cut a remote cable of a suitable
length.
2
Strip off about 6 cm of the sheath from the end of the cable, and strip off about 5 mm of
the insulation of the wire.
3
Insert the drain wire into the heat-shrinkable tubing, and shrink the heat-shrinkable
tubing by applying an appropriate amount of heat to it. (If there is no heat-shrinkable
tubing, take measures so that the drain wire can be insulated from the other wires.)
4
Crimp the wires and the RAV1.25-4 crimp terminals (wire diameter 1.25 mm, M4 round
crimp terminals) with an appropriate crimping tool.
Figure 2-19. Adjusting the Length of the Cable
Caution
•
When connecting or disconnecting positioner body cables, do not allow contami-
nants, rainwater, and the like to enter the valve travel detector unit or the positioner
body.
•
Periodically tighten the watertight gland and flameproof cable gland. Failure to do
so may allow rainwater to enter the equipment, resulting in malfunctions.
•
The cable cannot be removed from the valve travel detector unit. However, the wa-
tertight gland can be removed.
•
Do not remove the flameproof cable gland on the valve travel detector. Doing so
could cause wires inside the cable to be broken as a result of the rotation of the
cable.
Summary of Contents for AVP200
Page 30: ......
Page 66: ...2 28...
Page 80: ...4 4 Menu Tree...
Page 120: ...5 16...
Page 128: ...6 8 For models those date of manufacture are before September 2017...
Page 130: ...6 10 For models those date of manufacture are before September 2017...
Page 132: ...6 12 For models those date of manufacture are before September 2017...
Page 136: ...6 16 For models those date of manufacture are after October 2017...
Page 138: ...6 18 For models those date of manufacture are after October 2017...
Page 184: ...Appendix A Specifications A 25...
Page 185: ......
Page 188: ......
Page 190: ......