7-34
■
Constant value control data setting
0: Program run mode
1: Constant value control mode
[Description:]
When setup
C21
is set to 0, this setting is automatically
set to 0.
0
ConSt
1
Control mode
Within the range of setup
C66
to
C67
(SP limit)
0
SP
2
Setpoint
0.0 to 1000.0%
A setting of 0.0 turns on ON-OFF control
100.0
P
3
Proportional band
0 to 3600sec
No integral operation when set to 0.
[Description:]
When
P
is set to 0.0, “-----” is displayed and setting is not possible.
0
I
4
Integral time
0 to 1200 sec
No integral operation when set to 0.
[Description:]
When
P
is set to 0.0, “-----” is displayed and setting is not possible.
0
d
5
Derivative time
0.0 to 100.0%
[Description:]
When
P
is set to 0.0, “-----” is displayed and setting is not
possible.When I is not equal to 0, “-----” is displayed and setting
is not possible.
50.0
rE
6
Manual reset
-5.0% to upper limit
0.0
oL
7
Manipulated variable lower limit
Lower limit to +105%
100.0
oH
8
Manipulated variable upper limit
Item code
Item
No.
User
settings
Settings and descriptions
Factory default
settings
Chapter 7. PARAMETER SETUP