10-6
●
General reset is not possible with FUNC, CLR and MESSAGE keys
■
Parameter setting related problems
●
Registration state cannot be invoked with ENTER key
■
Program setting related problems
●
Registration state cannot be invoked with ENTER key
●
Item changes cannot be made with
and
keys
●
SP values in program settings cannot be changed with
and
keys
●
Event items cannot be displayed with
and
keys
Cause
Measure
Event type is something other than segment
type.
Set the event type in the event configuration data to a value
between 1 and 23.
Programming item sets no display.
Set setup data
C57 to 0.
Cause
Measure
SP limit sets error value.
Set correct value for setup data
C66 and C67.
Cause
Measure
Not pattern item set.
Set SP and time data.
Cause
Measure
Set to memory protect.
Set variable parameter
PA02 to 0, 2 or 4.
Cause
Measure
“-----” displayed in display panel 2
This item cannot be displayed or set. To change setting
connection item, it may be able to change or set.
Data displayed in display panel 2 cannot be changed. This item is display only.
Set to memory protect.
Set variable parameter
PA02 to 0.
Cause
Measure
Normal display mode not on
Press
DISP key
to invoke normal display mode.
Mode other than READY mode
Set READY mode to execute RESET operation (
PROG +
RUN/HOLD keys
).
Set to MANUAL mode.
Set AUTO mode to execute AUTO operation (
A/M key
).
Set to memory protect.
Set variable parameter
PA02 to 0.
Set to key lock.
Set variable parameter
PA01 to 0.
Chapter 10. MAINTENANCE AND TROUBLESHOOTING