AB-5702 

10 

Mounting hole dimensions (for mounting with the optional bracket) 

 

 

 

 

 

 

 

 

 

Figure 5.  Mounting hole (mm) 

 
Setting (Addressing and Functional Setting) 

1)  Remove the switch cover. 

Refer to the figure on the right to remove 
the switch cover. 

 

 

 

 

2)  Set the address. 

Turn the rotary switches located on the lower right of the front face, using a precision Phillips or slotted screwdriver, to set 
the SC-bus controller number as address.  The second digit of the address is set by the switch on the left and the first digit 
of the address is set by the switch on the right.  Set the number within the range from 1 to 50 for address. 

 

3)  Change the functions. 

Slide the DIP switch of the DIO and DI models located on the lower right of the front face, using a precision slotted 
screwdriver, to switch the functions (to change point configurations). 

 

Functions and DIP switch settings of DIO model 

Functions and DIP switch settings of DI model 

Function (point configuration) 

DIP switch 

setting 

Function (point configuration) 

DIP switch 

setting 

Start/stop point (maintained contact output) x 2 

0000 

Status, alarm point x 4 

0000 

Status point x 8 

0001 

Start/stop, status point (maintained contact output) 
x 2 

0001 

Alarm point x 8 

0010 

Status point x 4 + alarm point x 4 

0011 

Start/stop, status point (momentary contact output, 
without unmatched alarm monitoring) x 2 

0010 

Start/stop, status point (momentary contact output, 
with unmatched alarm monitoring) x 2 

0011 

Start/stop, status, alarm point (maintained contact 
output) x 2 

0101 

Start/stop, status, alarm point (momentary contact 
output, without unmatched alarm monitoring) x 2 

0110 

Start/stop, status, alarm point (momentary contact 
output, with unmatched alarm monitoring) x 2 

0111 

 

Setting image of the DIP switch  
(example of setting at "0001") 

 

Figure 7.  DIP switch setting image 

Note: 

Do not change the factory-preset DIP switch "1000" of TOT model though TOT model also has the DIP switch. 

 

4)  Attach the switch cover. 

Engage the release tab of the switch cover with the housing and press the bottom of the switch cover (See Fig. 6.) to attach. 

 

Four M4 x L8 tapping screws

112 ±0.3 

50 ±0.3 

Rotary switches 

for addressing

DIP switch for 

functional setting

Layout of the switches

Cover release tab

Switch cover

1. Press and hold. 

2. Disengage. 

Side view of the switches

Housing

Figure 6.  Switch cover removal 

Summary of Contents for WY7208W Series

Page 1: ...g with the rotary switch and functional setting with the DIP switch no other setting is required for setup Model Numbers Model number Description WY7208W1120 DIO model Select from the following point...

Page 2: ...ns WARNING Be sure to ground the product with ground resistance of less than 100 Improper grounding might cause electric shock or malfunction Before detaching the terminal cover be sure to turn off th...

Page 3: ...ng so might cause device failure When replacing the battery read the instructions hereinafter and correctly attach the new battery to the product Failure to do so might cause overheating burst or leak...

Page 4: ...dedicated LAN general office purpose LAN CDGP AI Pt TOT model Model WY7208W4140 WY7208W6140 WY7208W3180 Sensor Meter Infilex FC Model WY5205W8000 WY5205W9000 FCU User terminal Model QY7205 QY7290 FCU...

Page 5: ...ime Min 30 ms OFF time Min 100 ms ON OFF time Applied current voltage 5 mA DC typ 12 V DC typ Connectable output Dry contact transistor output open collector output Memory backup Replaceable lithium b...

Page 6: ...AB 5702 6 Dimensions DIO DI AI RRD and Pt models Figure 2 Dimensions DIO DI AI RRD and Pt models TOT model Figure 3 Dimensions TOT model 60 75 95 65 95 65 60 75 19 5...

Page 7: ...grams do not show the appropriate mounting orientation DIO model Point configurations and point assignment to the terminals DIO model Point configuration DO1 1 DO1 2 DI1 1 DI1 2 DO2 1 DO2 2 DI2 1 DI2...

Page 8: ...evice in connection From device in connection From device in connection From device in connection From device in connection Note If the output of the device in connection has polarity connect 0 V wire...

Page 9: ...CN3 SC bus CN4 SC bus From Pt100 temperature sensor From Pt100 temperature sensor From Pt100 temperature sensor To another sub controller Min 20 2 75 x n 35 DIN rail width Min 20 1 2 Min 50 95 Min 50...

Page 10: ...act output x 2 0000 Status alarm point x 4 0000 Status point x 8 0001 Start stop status point maintained contact output x 2 0001 Alarm point x 8 0010 Status point x 4 alarm point x 4 0011 Start stop s...

Page 11: ...r a year or over replace the battery before turning on the CDGP IMPORTANT Lithium battery replacement of TOT model Replace the battery while the CDGP TOT model is being powered Failure to do so will e...

Page 12: ...RD model using the remote control relay and the remote control breaker For providing these devices and the remote control switch thoroughly read the instructions supplied by their manufacturers Do not...

Reviews: