AB-5702
11
Maintenance
CAUTION
When replacing the battery, read the instructions hereinafter and correctly attach the new battery to the product.
Failure to do so might cause overheating, burst, or leakage of the battery.
Dispose of the used battery in accordance with your local regulations.
Do not throw it in fire or in general garbage.
Doing so might cause burst or ignition.
TOT model has the lithium battery for memory backup. Replace the battery approximately once every five years (Part No.
83170623). Note that the battery must be replaced while the CDGP (TOT model) is being powered. Be sure to save the backup
data stored in the CDGP before replacing the battery in case of data loss. If the CDGP without being powered is left for a year
or over, replace the battery before turning on the CDGP.
IMPORTANT:
Lithium battery replacement of TOT model
●
Replace the battery while the CDGP (TOT model) is being powered. Failure to do so will erase the backup
data.
●
Do not disconnect the battery connector except when replacing the lithium battery. If you connect the battery
connector while the CDGP is OFF, the CDGP will not switch the operation mode to the low power mode and
will run out of the battery in a few days.
Removing the lithium battery of TOT model
1) Remove the switch cover.
Refer to the
Setting
section for removing the switch cover. (See Fig. 6.)
Figure 8. Switch cover removal
2) Open the battery case.
3) Take out the battery and disconnect the battery connector.
Battery case
Release tab
Switch cover
Battery case
(closed)
Press here
to open.
Figure 9. Battery case
Battery case
(open)
Lithium battery
Connector
Lead wire
Disconnect.
Figure 10. Lithium battery removal