AB-5702
4
System Configurations
CDGP for BMS
For BMS and devices that are compatible to CDGP, ask our salesperson.
For AI and Pt models of CDGP, up to 20 CDGP are connectable to Infilex ZM via SC-bus.
CDGP for a simple system
Figure 1. System configuration examples
IMPORTANT:
To prevent fire, electric shock, injury, or other damage in the event that this product fails, the customer's
system should provide foolproof, fail-safe, and safety design that includes countermeasures to the spread of
fire and ensures the required degree of reliability and safety.
Web browser
in your PC
SC-bus (Max. 99 units and 1000 m)
CDGP
DIO/DI/RRD model
Model WY7208W1120/
WY7208W2180/WY7208W5140
Chiller plant equip.
/Plumbing equip.
/Lighting equip.
SmartScreen
™
Ethernet
SmartScreen
dedicated LAN,
general office
purpose LAN
CDGP
AI/Pt/TOT model
Model WY7208W4140/
WY7208W6140/WY7208W3180
Sensor/
Meter
Infilex
™
FC
Model WY5205W8000/
WY5205W9000
FCU
User terminal
Model QY7205/QY7290
FCU: Fan coil unit
Other connectable devices to NC-bus:
DIF-II/Energy meter
Infilex
™
GC
Model WY5111
Infilex
™
GD
Model WY5110
NC-bus (Max. 25 units and 500 m, but extendable up to 1000 m with the repeater module.)
SC-bus (Max. 50 units and 1000 m)
CDGP
DIO model
Infilex
™
ZM
Model WY5122
DDC controller
for FCU
Infilex
™
ZM
Model WY5122
CDGP
DI model
Infilex
™
FC
Model WY5205
Infilex
™
VC
Model WY5206
Model WY7208W1120 Model WY7208W2180
CDGP
TOT model
CDGP
AI model
Model WY7208W3180 Model WY7208W4140
CDGP
RRD model
CDGP
Pt model
Model WY7208W5140 Model WY7208W6140
DDC controller
for VAV
BACnet
®
IP
Client PC
BMS: Building management system
DDC: Direct digital control
DIF-II: DGP (Data Gathering Panel) Line Interface II
FCU: Fan coil unit
VAV: Variable air volume unit
BMS