AB-5702 

System Configurations 

CDGP for BMS 
For BMS and devices that are compatible to CDGP, ask our salesperson. 
For AI and Pt models of CDGP, up to 20 CDGP are connectable to Infilex ZM via SC-bus. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CDGP for a simple system 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 1.  System configuration examples 

 

IMPORTANT: 
  To prevent fire, electric shock, injury, or other damage in the event that this product fails, the customer's 

system should provide foolproof, fail-safe, and safety design that includes countermeasures to the spread of 
fire and ensures the required degree of reliability and safety. 

 

Web browser 

in your PC 

SC-bus (Max. 99 units and 1000 m)

CDGP 

DIO/DI/RRD model 

Model WY7208W1120/ 

WY7208W2180/WY7208W5140 

Chiller plant equip. 

/Plumbing equip. 

/Lighting equip. 

SmartScreen

 

Ethernet 

SmartScreen 

dedicated LAN, 

general office 

purpose LAN

 

CDGP 

AI/Pt/TOT model

Model WY7208W4140/ 

WY7208W6140/WY7208W3180

Sensor/ 

Meter 

Infilex

 FC 

Model WY5205W8000/

WY5205W9000

FCU 

User terminal 

Model QY7205/QY7290 

FCU: Fan coil unit 

Other connectable devices to NC-bus: 
DIF-II/Energy meter 

Infilex

 GC 

Model WY5111

 

Infilex

 GD

Model WY5110

NC-bus (Max. 25 units and 500 m, but extendable up to 1000 m with the repeater module.)

SC-bus (Max. 50 units and 1000 m)

CDGP 

DIO model 

Infilex

 ZM

Model WY5122

DDC controller 

for FCU 

Infilex

 ZM 

Model WY5122

 

CDGP 

DI model 

Infilex

 FC 

Model WY5205

 

Infilex

 VC

Model WY5206

Model WY7208W1120 Model WY7208W2180 

CDGP 

TOT model 

CDGP 

AI model 

Model WY7208W3180  Model WY7208W4140

CDGP 

RRD model

CDGP 

Pt model 

Model WY7208W5140 Model WY7208W6140 

DDC controller 

for VAV 

BACnet

®

 IP

Client PC 

BMS: Building management system 
DDC: Direct digital control 
DIF-II: DGP (Data Gathering Panel) Line Interface II 
FCU: Fan coil unit 
VAV: Variable air volume unit 

BMS 

Summary of Contents for WY7208W Series

Page 1: ...g with the rotary switch and functional setting with the DIP switch no other setting is required for setup Model Numbers Model number Description WY7208W1120 DIO model Select from the following point...

Page 2: ...ns WARNING Be sure to ground the product with ground resistance of less than 100 Improper grounding might cause electric shock or malfunction Before detaching the terminal cover be sure to turn off th...

Page 3: ...ng so might cause device failure When replacing the battery read the instructions hereinafter and correctly attach the new battery to the product Failure to do so might cause overheating burst or leak...

Page 4: ...dedicated LAN general office purpose LAN CDGP AI Pt TOT model Model WY7208W4140 WY7208W6140 WY7208W3180 Sensor Meter Infilex FC Model WY5205W8000 WY5205W9000 FCU User terminal Model QY7205 QY7290 FCU...

Page 5: ...ime Min 30 ms OFF time Min 100 ms ON OFF time Applied current voltage 5 mA DC typ 12 V DC typ Connectable output Dry contact transistor output open collector output Memory backup Replaceable lithium b...

Page 6: ...AB 5702 6 Dimensions DIO DI AI RRD and Pt models Figure 2 Dimensions DIO DI AI RRD and Pt models TOT model Figure 3 Dimensions TOT model 60 75 95 65 95 65 60 75 19 5...

Page 7: ...grams do not show the appropriate mounting orientation DIO model Point configurations and point assignment to the terminals DIO model Point configuration DO1 1 DO1 2 DI1 1 DI1 2 DO2 1 DO2 2 DI2 1 DI2...

Page 8: ...evice in connection From device in connection From device in connection From device in connection From device in connection Note If the output of the device in connection has polarity connect 0 V wire...

Page 9: ...CN3 SC bus CN4 SC bus From Pt100 temperature sensor From Pt100 temperature sensor From Pt100 temperature sensor To another sub controller Min 20 2 75 x n 35 DIN rail width Min 20 1 2 Min 50 95 Min 50...

Page 10: ...act output x 2 0000 Status alarm point x 4 0000 Status point x 8 0001 Start stop status point maintained contact output x 2 0001 Alarm point x 8 0010 Status point x 4 alarm point x 4 0011 Start stop s...

Page 11: ...r a year or over replace the battery before turning on the CDGP IMPORTANT Lithium battery replacement of TOT model Replace the battery while the CDGP TOT model is being powered Failure to do so will e...

Page 12: ...RD model using the remote control relay and the remote control breaker For providing these devices and the remote control switch thoroughly read the instructions supplied by their manufacturers Do not...

Reviews: