AB-5702 

 RRD model: All operating circuits powered by a single transformer 

 

 

 

 

 

 

 

 

 

 

 

 Pt model 

 

 

 

 

 

 

 

 

 

 

 

Installation 

 CAUTION 

 

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

 

Mounting dimensions 

Hatched area shows maintenance clearance. 

Mounting 

on 

DIN 

rail 

    Mounting 

with 

our optional bracket (Part No. 83160917-001) 

 

 

 

 

 

 

 

 

 

 

 

Notes: 
*1  Leave 100 mm or more clearance for TOT model. 
*2  For multiple ("n" in the figures above) CDGP, tightly mount them without gap, and leave the clearance on the both ends of CDGP. 

Figure 4.  Mounting dimensions (mm) 

CDGP 

 7 

10 

11 

12 

13 

14 

15 

From Pt100 temperature sensor

85 to 264 V AC 

Grounding 

(Max. 100 

 

ground resistance) 

1Pt 

2Pt 

3Pt 

4Pt 

To another 

sub controller 

CN3 

SC-bus 

CN4 

SC-bus 

From Pt100 temperature sensor

From Pt100 temperature sensor 

From Pt100 temperature sensor 

To another 

sub controller 

Min. 20*

2

 

75 x n 

35 

(DIN r

ail width)

 

Min. 20*

1, 2

 

Min. 50 

95 

Min. 50 

112 

75 x n 

Min. 30*

2

 

Min. 30*

2

 

50 

122 

95 

Min. 50

Min. 50

Optional
bracket

    Remote control switch *2

White

 

Red

    Remote control

 

breaker

Red

Blue

Blue

White

    Remote control

 

breaker

Red 

Blue

    Remote control

 

breaker

Red

Blue

    Remote control

 

breaker

Red

Blue

CDGP 

CN4 

CN3 

To another 

sub controller

Grounding

(Max. 100 

ground resistance)

85 to 264 V AC

To another 

sub controller

SC-bus OUT

SC-bus IN 

*1 

RRD1

10 

11 

12 

13 

14 

15 

*1 

RRD2

*1 

RRD3

*1 

RRD4

Remote control 
transformer

100V AC or 200V AC 

Notes: 
 *1 Terminals 5-6, 8-9, 11-12, and 14-15 are 

internally connected. 

 *2 Up to four remote control switches can be 

paralleled. 

*3  The diagram on the left is an example of 

connecting the remote control breakers.  For 
the remote control relays, connect the same 
way. 

*3

*3

*3

*3

Summary of Contents for WY7208W Series

Page 1: ...g with the rotary switch and functional setting with the DIP switch no other setting is required for setup Model Numbers Model number Description WY7208W1120 DIO model Select from the following point...

Page 2: ...ns WARNING Be sure to ground the product with ground resistance of less than 100 Improper grounding might cause electric shock or malfunction Before detaching the terminal cover be sure to turn off th...

Page 3: ...ng so might cause device failure When replacing the battery read the instructions hereinafter and correctly attach the new battery to the product Failure to do so might cause overheating burst or leak...

Page 4: ...dedicated LAN general office purpose LAN CDGP AI Pt TOT model Model WY7208W4140 WY7208W6140 WY7208W3180 Sensor Meter Infilex FC Model WY5205W8000 WY5205W9000 FCU User terminal Model QY7205 QY7290 FCU...

Page 5: ...ime Min 30 ms OFF time Min 100 ms ON OFF time Applied current voltage 5 mA DC typ 12 V DC typ Connectable output Dry contact transistor output open collector output Memory backup Replaceable lithium b...

Page 6: ...AB 5702 6 Dimensions DIO DI AI RRD and Pt models Figure 2 Dimensions DIO DI AI RRD and Pt models TOT model Figure 3 Dimensions TOT model 60 75 95 65 95 65 60 75 19 5...

Page 7: ...grams do not show the appropriate mounting orientation DIO model Point configurations and point assignment to the terminals DIO model Point configuration DO1 1 DO1 2 DI1 1 DI1 2 DO2 1 DO2 2 DI2 1 DI2...

Page 8: ...evice in connection From device in connection From device in connection From device in connection From device in connection Note If the output of the device in connection has polarity connect 0 V wire...

Page 9: ...CN3 SC bus CN4 SC bus From Pt100 temperature sensor From Pt100 temperature sensor From Pt100 temperature sensor To another sub controller Min 20 2 75 x n 35 DIN rail width Min 20 1 2 Min 50 95 Min 50...

Page 10: ...act output x 2 0000 Status alarm point x 4 0000 Status point x 8 0001 Start stop status point maintained contact output x 2 0001 Alarm point x 8 0010 Status point x 4 alarm point x 4 0011 Start stop s...

Page 11: ...r a year or over replace the battery before turning on the CDGP IMPORTANT Lithium battery replacement of TOT model Replace the battery while the CDGP TOT model is being powered Failure to do so will e...

Page 12: ...RD model using the remote control relay and the remote control breaker For providing these devices and the remote control switch thoroughly read the instructions supplied by their manufacturers Do not...

Reviews: