Steps

Procedures

Description

LCD Display

Step 1

To start setting, press the 

SET 

key for 3 seconds to access the setpoint mode. The LCD 

will display the current setpoint (flashing). Then press either the 

Up 

key to increase or 

the 

Down 

key  to  decrease  the  setpoint  to  the  desired  setting. An  example  of  LCD 

display in AF mode is shown.

Setpoint Temperature

 

Default setting: 70 F(21 C) 
for A or AF mode, 82 F(28 C) 
for F mode. 

°

°

°

°

Step 2

Press 

SET

 key again to access the differential mode. The LCD will display the current 

differential (blinking). Then press either the 

Up 

key to increase or the 

Down 

key to 

decrease the differential to the desired setting. Selection value: 0.5, 1.0, 1.5, 2.0

Differential Temperature 

Default setting: 1 F(1 C)

°

°

Step 3

(A mode only, 
otherwise, skip 
this step)

Press 

SET

 key again to access the Outdoor sensor. LCD will display the current 

setting: Off (blinking) Then press either the 

Up 

key or 

Down

 key to toggle between 

On and Off.

Outdoor sensor: On or Off

Default setting: Off

Step 4

(AF mode only, 
otherwise skip 
this step)

Press 

SET 

key again to access the Maximum Floor limit. The LCD will display the 

current setting (blinking). Then press either the 

Up 

key to increase or the 

Down

 key 

to decrease the limit to the desired setting.

Floor maximum limit

Default setting: 
82 F(28 C)

°

°

Step 5

(AF mode only, 
otherwise skip 
this step)

Press 

SET 

key again to access the Minimum Floor limit. The LCD will display the 

current setting (blinking). Then press either the 

Up 

key to increase or the 

Down

 key 

to decrease the limit to the desired setting.

Floor minimum limit

Default setting: 40 F(5 C)

°

°

Step 6

Press 

SET

 key again to access the System Mode. LCD will display the current 

mode: Heat (blinking) Then press either the 

Up 

key or 

Down

 key to toggle between 

Heat and Off.

System Mode: Heat or Off

Default setting: Heat

Step 7

Press 

SET

 key again to access the backlit mode. LCD will display the current mode, 

Auto (blinking). Then press either the 

Up 

key or the 

Down

 key to toggle etween the 

Auto, On, Off designation. Press 

SET 

key again to go back to normal operating 

mode. Note: In Auto Mode, backlit is turned on for 60 seconds when any key is 
pressed.

 b

Backlit mode: Auto, On or 
Off

Default setting: Auto

View 

Mode:

Press both 

Up

 and 

Down 

keys at the same time to review the current control 

settings.  “VIEW  MODE”  appears  on  the  upper  left  corner  of  the  LCD.  Then 
Press 

(or 

Up

) key to scroll through the settings in the same order as 

Setting Mode (Setpoint, Differential, Heat/Off, Backlit etc.). To exit to normal 
mode, press 

one more time   from the last setting (e.g. Backlit) or 

press  both

  Up

  and 

at  the  same  time.  In  this  mode,  the  settings 

cannot be changed.

Setting 

Down 

Down 

key 

Down 

keys

 

Keypad Lock:

Keypad  can be locked to prevent tempering by unauthorized personnel. This is 
done by pressing 

SET

 , 

Up

 and 

Down 

keys at the same time for three seconds. 

A  lock  symbol  appears  on  the  lower  LCD  screen  which  indicates  that  the 
keypad is locked. Then input from the keypad is disabled.  Press 

SET

Up 

and 

Down 

keys at the same time again for another three seconds to unlock the 

keypad. The lock symbol disappears from the screen. 
Factory setting: unlock

Turning On and Off  the Heating System

In the heat mode, the relay is operated to maintain the temperature of the zone. 

The control output will turn on when the sensor temperature falls to the setpoint 
temperature minus half the differential amount. The control output will turn off as 
the temperature rises to the setpoint plus half the differential amount.

During the normal operating mode:

!

  To disable or enable the relay output, press the power button once(eg. 1 

second).  LCD  indicates  a  flashing  “Heat”  or  “Off”  under  the  “System” 
heading. Press the power button again to toggle between “Heat” to enable 
and “Off” to disable the relay output. After 30 seconds, the system returns to 
normal operating mode.

!

To completely power off the thermostat, press the power button for three 

seconds. Press the power button again to turn back on the thermostat.

:

Sensor Error

    

Er3

EEPROM (memory) data has been corrupted. 
Replace the thermostat.

HHH

The measured temperature is above the upper 
display range.

LLL

The measured temperature is below the lower 
display range.

Room

°

F

AF

SET MODE

  70

SET MODE

°

F

    1

8if

A

On

OutDoor

82

AF

°

F

Floor  Max 

40

Floor          Min

°

F

Floor   

AF

SYSTEM

Heat

Backlit:         Auto

Error Messages

Sensor Error

   

 Er1

Internal sensor is open or short circuit. Replace the 
thermostat

Sensor Error

   

 Er2

s

   External sensor is open or short circuit. Replace 

the external sensor.

s

   In A mode, if outdoor sensor is set to ON and no 

sensor is connected.

SPECIFICATIONS:

Display Format: Liquid Crystal Display(LCD) with backlit

    Power Input : 24VAC 

, 50/60Hz, 0.5VA

    Selectable display in °F or °C
   
    Floor Temperature Control Range: 34-122°F(1-50°C) 

Default setting: 

    Maximum Floor Temperature Limit(AF Mode): 35-122°F(2-50°C) 

Default: 82°F(28°C)

    Minimum Floor Temperature Limit(AF Mode): 34-121°F(1-49°C) 

Default: 40°F(5°C). 

   Switching Differential: A/F/AF Mode: 0.5/1.0/1.5/2°F(

, Default: 1°F/1°C. 

    Sensor Probe: P-01 10k

thermistors, 10" lead, 3/8"(9.5mm) OD x 

13/16"(20.6mm) length

   

s
s
s
s
s
s

s

s

s
s

s
s
s
s
s
s
s

±10%

Contact Rating: 2A 24VAC

34-100°F(1-38°C)

°

°

°

°

s

    Temperature Display Range: -22 to 131°F(-30 to 55°C)

°C)

Operating Temperature: 32 - 122°F (0 - 50°C)
Dimension: 3.62"W x 2.99"H x 0.91"D(92 x 76 x 23mm)
Weight: 0.32 lb. (145 g)
Storage: -4 to 120°F  (-20 to 50°C) 
Material: Flame retardant plastic
Lockout mode to prevent tempering by unauthorized personnel
EEPROM memory retains control settings in the event of a power 
failure.

Setpoint Range (ambient): 

. Default setting: 70 F (21 C)

 82 F (28 C)

?  

 

A

ZEL

TECHNOLOGIES INC.

P.O. Box 53138,  10 Royal Orchard Blvd.

Thornhill, Ontario, Canada L3T 7R9

Ph: 905-223-5567     Fax: 905-223-3778

Email: info@azeltec.com

For more product information, please visit:

www.azeltec.com

SET MODE

SET MODE

SET MODE

SET MODE

SET MODE

SET MODE

SET MODE

SET MODE

SET MODE

SET MODE

SET MODE

SET MODE

Sensor

Reviews: