Rev: 03/2009
KNX-GSM Gateway
Page 16 of 19
©
b+b Automations- und Steuerungstechnik GmbH
KNX-GSM GATEWAY.DOC
If you want to get the incoming value inside the SMS, you can activate the option „Append current
value to message text“.
In the middle area you define when the SMS should be send, the following event types are possible:
-
Receiving a value
- Receiving
0
- Receiving
1
- Receiving
0
Æ
x
- Receiving
x
Æ
0
-
Value below lower limit
-
Value in range
-
Value outside range
-
Value above upper limit
The last four events need additional lower/upper limit values. Please take care that the limits are
matching the selected EIB data type.
The limit/range events will by default only triggered, if the limit/range condition has been reached the
first time. If you for example are using “Value below lower limit”, and the temperature is falling into
this range, a SMS will be send. If the temperature doesn’t leave this lower area, no new messages
will be send. If you want a message on every incoming value, you have to activate the option “Send
always”.
You can also lock each message to a time range. If you select „Send SMS independed from current
time“, the message will be send always. If you select the “Send only … in / out time range“, you can
additionally create and select a time range fort his message. Up to eight time ranges are possible;:
After you have defined your message, pressing “OK” will add it to the list in the main window: