8. Layout of the circuit board

Fig.   8

 1

  Spring-force auxiliary voltage terminal, suitable for solid 

conductor up to 1.5 mm² or fine wire conductor

2

  Slot for cable connection to the precipitation sensor in the 

casing lid

GPS antenna

4

 Signal LED

KNX te/-

6

 Program button for setting up the device

7

 Program LED

 1

3

2

4

5

6

7

9. Mounting the weather station

Close the housing by putting the cover back over the bottom part. 

The cover must snap in on the left and right with a definite “click”.

Fig. 9

Raste

Make sure the cover and bottom part are properly 

snapped together! This picture is looking 

at the closed sensor from underneath.

Fig. 10

Push the housing from above into the fastened mount. The 

bumps on the mount must snap into the rails in the housing.

To remove it, the weather station can be simply pulled upwards 

out of the mount,against the resistance of the fastening.

 13. Technical Data

Housing:                             

Housing UV- and shockresistant  

 

 

   Polycarbonate

Degree of protection/class:    

IP44 / II / CE

Dimensions W,H, D [mm]:     

96 × 77 ×  1 18

 

Ambient temperature:     

-30° to +50°

Auxiliary voltage:                

12 to 40 V DC,  12 to 28 V AC

Hilfsstrom:                          

max.  185 mA at  12 V DC,

                                      max. 8 1 mA at 24 V DC,
 

                          Residual ripple  10%

Bus current: 

   

max. 8 mA

Data output: 

            

KNX +/- 

Group addresses:               

max. 254

Assignments: 

              

max. 255

Communication objects:      

254

Heater rain sensor:             

ca.  1,2 W

Measurement range  

temperature: 

    

-30° to +80°C

Resolution (temperature):      

0, 1°C

Accuracy (temperature):       

± 1°C at - 10°C to +85°C,

                                     ± 1,5°C at -25° to + 150°C

Measurement  

range wind: 

 

0 to 35 m/s

 

Resolution (wind):               

0, 1m/s

Accuracy (wind):

  at ambient temperature -20 to +50°C:

 

          ±22% of the measurement value when  

                       incident flow is from 45 to 3 15° 
                       ± 15% of the measurement value when incident
                       flow is from 90 to 270° (Frontal incident flow                 

                       corresponds to  180°)

Measurement range  

brightness: 

       

0 to  150.000 Lux

Resolution  (brightness):  

     1 Lux at 0 at  120 Lux,

 

                   2 Lux at  12 1 at  1.046 Lux,

 

                         63 Lux at  1.047 at 52.363 Lux,

 

                              423 Lux at 52.364 at  150.000 Lux

Accuracy (brightness):       

±20% at 0 lx …  10 klx,

 

                   ± 15% at  10 klx …  150 klx

  

Declaration of Conformity: 

The product complies with the 

low voltage recommendation 2006/95/EG and the EMV 

recommendation 2004/108/EG.

The following standards have been applied:

• 

EN 50491-5-1: 2010

• 

EN 50491-5-2: 2011

11. Maintenance

The sensor must regularly be checked for dirt twice a year and 

cleaned if necessary. In case of severe dirt, the sensor may not 

work properly anymore.

!

  

As a precaution, the device should always be separated 

from power supply for maintenance works (e.g. deacti-

vate or remove fuse).

1 2. 

Article / Part nr. / Accessory

Typ

SM

KNX WTS-GPS

90221

 10. Notes on mounting and commissioning

Do not open weather station if water (rain) might ingress: even 

some drops might damage the electronic system.
Observe the correct connections. Incorrect connections may 

destroy the weather station or connected electronic devices.
Please take care not to damage the temperature sensor (small 

blank at the bottom part of the housing.) when mounting the 

weather station. Please also take care not to break away or 

bend the cable connection between the blank and the rain 

sensor when connecting the weather station.
Remove all existing protection labels after installation.
The measured wind value and thus all other wind switching 

outputs may only be supplied 60 seconds after the supply volt-

age has been connected.
After the auxiliary voltage has been applied, the device will en-

ter an initialisation phase lasting 5 seconds. During this phase 

no information can be received via the bus.

Fig.   7

Place the sheath of the cable under the board and 

allow only the connection cables through the holes 

in the circuit board to the top.

Ensure that the sheath of the cable remains below the PCB 

board and only the connection cables go through the rubber 

seals on the bottom of the weather station and connect Voltage 

and Bus +/- to the terminals provided.

Catch