0 13
– 1
8. Layout of the circuit board
Fig. 8
1
Spring-force auxiliary voltage terminal, suitable for solid
conductor up to 1.5 mm² or fine wire conductor
2
Slot for cable connection to the precipitation sensor in the
casing lid
3
GPS antenna
4
Signal LED
5
KNX te/-
6
Program button for setting up the device
7
Program LED
1
3
2
4
5
6
7
9. Mounting the weather station
Close the housing by putting the cover back over the bottom part.
The cover must snap in on the left and right with a definite “click”.
Fig. 9
Raste
Make sure the cover and bottom part are properly
snapped together! This picture is looking
at the closed sensor from underneath.
Fig. 10
Push the housing from above into the fastened mount. The
bumps on the mount must snap into the rails in the housing.
To remove it, the weather station can be simply pulled upwards
out of the mount,against the resistance of the fastening.
13. Technical Data
Housing:
Housing UV- and shockresistant
Polycarbonate
Degree of protection/class:
IP44 / II / CE
Dimensions W,H, D [mm]:
96 × 77 × 1 18
Ambient temperature:
-30° to +50°
Auxiliary voltage:
12 to 40 V DC, 12 to 28 V AC
Hilfsstrom:
max. 185 mA at 12 V DC,
max. 8 1 mA at 24 V DC,
Residual ripple 10%
Bus current:
max. 8 mA
Data output:
KNX +/-
Group addresses:
max. 254
Assignments:
max. 255
Communication objects:
254
Heater rain sensor:
ca. 1,2 W
Measurement range
temperature:
-30° to +80°C
Resolution (temperature):
0, 1°C
Accuracy (temperature):
± 1°C at - 10°C to +85°C,
± 1,5°C at -25° to + 150°C
Measurement
range wind:
0 to 35 m/s
Resolution (wind):
0, 1m/s
Accuracy (wind):
at ambient temperature -20 to +50°C:
±22% of the measurement value when
incident flow is from 45 to 3 15°
± 15% of the measurement value when incident
flow is from 90 to 270° (Frontal incident flow
corresponds to 180°)
Measurement range
brightness:
0 to 150.000 Lux
Resolution (brightness):
1 Lux at 0 at 120 Lux,
2 Lux at 12 1 at 1.046 Lux,
63 Lux at 1.047 at 52.363 Lux,
423 Lux at 52.364 at 150.000 Lux
Accuracy (brightness):
±20% at 0 lx … 10 klx,
± 15% at 10 klx … 150 klx
Declaration of Conformity:
The product complies with the
low voltage recommendation 2006/95/EG and the EMV
recommendation 2004/108/EG.
The following standards have been applied:
•
EN 50491-5-1: 2010
•
EN 50491-5-2: 2011
11. Maintenance
The sensor must regularly be checked for dirt twice a year and
cleaned if necessary. In case of severe dirt, the sensor may not
work properly anymore.
!
As a precaution, the device should always be separated
from power supply for maintenance works (e.g. deacti-
vate or remove fuse).
1 2.
Article / Part nr. / Accessory
Typ
SM
KNX WTS-GPS
90221
10. Notes on mounting and commissioning
Do not open weather station if water (rain) might ingress: even
some drops might damage the electronic system.
Observe the correct connections. Incorrect connections may
destroy the weather station or connected electronic devices.
Please take care not to damage the temperature sensor (small
blank at the bottom part of the housing.) when mounting the
weather station. Please also take care not to break away or
bend the cable connection between the blank and the rain
sensor when connecting the weather station.
Remove all existing protection labels after installation.
The measured wind value and thus all other wind switching
outputs may only be supplied 60 seconds after the supply volt-
age has been connected.
After the auxiliary voltage has been applied, the device will en-
ter an initialisation phase lasting 5 seconds. During this phase
no information can be received via the bus.
Fig. 7
Place the sheath of the cable under the board and
allow only the connection cables through the holes
in the circuit board to the top.
Ensure that the sheath of the cable remains below the PCB
board and only the connection cables go through the rubber
seals on the bottom of the weather station and connect Voltage
and Bus +/- to the terminals provided.
Catch