9. Range
12 m
3 m
10 m
180°
1,10 -2,20 m
Walking across
Walking towards
1
2
1
2
10. Exclude sources of interference
To hide the detection area below the detector ( f.e.animals/small
children), the enclosed Blind can be mounted or attached on it.
11. Technical data
11a. Technical data Indoor 180-R
Power supply:
110 – 240 VAC, 50/60 Hz
Power consumption:
approx. 0.5 W
Area of coverage:
semicircular 180°
Range of coverage
Ø H 1.10 m / T = 18°C:
tangential 10 m / radial 3 m
Max. mounting height:
2.2 m
Degree of protection/class:
IP20, with accessory IP54 / II
Ambient temperature:
-25°C – +50°C
Housing:
UV- and shock resistant
polycarbonate
Dimensions:
H 87 x W 87 mm (with cover frame)
• Channel 1 for light control
Switching power /
2300 W, cos φ= 1
contact
1150 VA, cos φ= 0,5
NOC/with pretravel tungsten
contact
Follow-up time:
15 sec. to 16 min. or pulse
Brightness threshold:
10 - 2000 Lux
11b. Technical data Indoor 180-T
Power supply:
110 – 240 VAC, 50/60 Hz
Power consumption:
approx. 1.3 W
Area of coverage:
semicircular 180°
Range of coverage
Ø H 1.10 m / T = 18°C:
tangential 10 m / radial 3 m
Max. mounting height:
2.2 m
Degree of protection/ class:
IP20, with accessory IP54 / II
Ambient temperature:
-25°C – +50°C
Housing:
UV- and shock resistant
polycarbonate
Dimensions:
H 87 x W 87 mm (with cover frame)
• Channel 1 for light control
Switching power /
only incandescant / halogen lamps
contact
min. 40 - max. 300 W, cos φ= 1
not suitable for LED loads!
Follow-up time:
15 sec. to 16 min. or pulse
Brightness threshold:
10 - 2000 Lux
Declaration of Conformity:
This product respects the directives concerning
1. electromagnetic compatibility (2014/30/EU)
2. low voltage (2014/35/EU)
3. restriction of the use of certain hazardous substances in
electrical and electronic equipment (2011/65/EU)
12. Article / Part-No. / Accessory
Type
Part-No.
Indoor 180-R, covering included
92623
Indoor 180-T, covering included
92622
Indoor 180-R, covering not included
92665
Indoor 180-T, covering not included
92664
Accessory:
Covering IP20
pure white, mat
92630
RAL9010
Covering IP20
traffic white, mat
92631
RAL9016
Covering IP20
oyster white, mat
92632
RAL1013
Covering IP20
silver, mat
92633
RAL9006
Covering IP20
anthracite, mat
92634
RAL7021
Covering IP54
pure white, mat
92139
RAL9010
SM-Socket for Indoor
pure white, brilliant
92141
RAL9010
Central plate
pure white, brilliant
39222
55x55mm
RAL9010
Central plate
traffic white, brilliant
39223
55x55mm RAL9016
Central plate
pure white, brilliant
35126
56x56mm (angular)
RAL9010
Central plate
pure white, brilliant
35127
56x56mm (rounded)
RAL9010
Central plate
traffic white, mat
38947
45x45mm
RAL9016
Central plate
cream white, mat
39076
45x45mm RAL9001
Blinds vertical/
transparent
92294
horizontal detection
13. LED-functional indicators
LED function indicators during operation
Process
LED function indicators
Mains power restored
Self-test: LED I flashes red
regularly for approx. 60 seconds
Motion detection
LED I flashes red on every
movement detected
Sound detection
LED II flashes red on every sound
detected
MAN 5
61
3 – 1
60
62
0-
7