Installation and Operating Instruction for 

B.E.G.

 - Occupancy detectors PD2-Master-DIM-SM/-FC/-FM

LUXOMAT

®

PD1-M-DIM

1

1

2

2

25 22

18

16

10

3

1

TEST

6

30

R1

120 6050

40

30

15

10

A

16 10

5

2

1

30

15

TEST

2000

1200

600

200

40

5

25 22

18

16

10

3

1

TEST

6

30

R1

2000

1200

600

200

40

GB

2a.  Installation of the LUXOMAT

®

 PD1-M-DIM-SM 

2b.  Installation of the LUXOMAT

®

PD1-M-DIM-FC

 1. Mounting preparations

Work on the 230 V mains supply 

may only be carried out by quali-

fied professionals or by instructed 

persons under the direction and 

supervision of qualified skilled elec-

trical personnel in accordance with 

electrotechnical regulations.

 

Disconnect supply before installing! 

 

When in Master/Slave mode of 

operation, the Master-appliance  

must always be installed at the  

location where there is least  

daylight.

2c.  Installation of the

LUXOMAT

®

 PD1-M-DIM-FM

The detector can 

be installed in 

conventional inlet-

sockets mounted 

on the ceiling.

The assembly 

plate enclosed 

must be stripped 

off prior to instal-

lation and secured 

to the ceiling 

using 4 screws 

and ensuring that 

it is not laterally 

transposed.

For surface-mounting, an inwall sensor unit is combined with a surface-mounted 

receptacle as a housing base.

Before mounting the base, the enclosed mounting plate must be mounted true to 

side, i.e. the writing must be legible. 

Now fix the base on ceiling or wall, but first put the cable through one of the 

cable openings provided. The detector must be mounted on a flat, solid surface.

Next prepare the sensor part by screwing in both fixing screws, then connect the 

cable as per the wiring diagram.

Now insert the sensor part and check for matching positioning 

of the two markings. 

Press beyond the spring housing pressure so that the sensor 

part firmly locks in place. 

Now turn the sensor part counter-clockwise for about 10° to 

the stop.

The detector has 

been designed and 

developed specifically 

for installation in sus-

pended ceilings. 

A circular opening of 

diameter 68 – 70 mm 

must be produced in 

the ceiling. 

Having connected up the cables in accor dance with 

regulations, the detector is inserted into the opening 

as shown in the drawing opposite and fixed into 

position with the assistance of the spring clips.

B.I.T

.

Q.C
.

PA

SSED

1

 

6 mm

Having connected up the cables in ac-

cordance with regulations, the detector 

can be placed in position as shown in the 

drawing opposite and, applying a little 

pressure, can then be locked into position 

with the assistance of the spring clips.

B.I.T

.

Q.C
.

PA

SSED

1

 

6 mm

4. Settings carried out using remote control (optional)

Remote control LUXOMAT

®

 IR-PDim

1. Check Battery:

 

open battery compartment by pressing the 

plastic springs together and removing the 

battery-holder.

2.  IMPORTANT 

Please pay attention, that the setting is Potentio-

meter 1 at “TEST” and Potentiometer 2 

not

 at 

“SUN”. All values which have been programmed 

using the remote control will be deleted in the 

event of power failure in the position “TEST/

SUN”. Please switch Potentiometer 2 over to 

“MOON” or any other value.

Caution:

 

Settings with remote control supersede the 

settings by courtesy of potentiometers.

 3. Putting into operation / Settings

Self test cycle 

The product enters an initial 60-second self-test cycle, when 

the supply is first connected. The occupancy detector is 

ready for operation.

Follow-up time for light control

 The time can be set infinitely variably at between  

1 and 30 minutes. 
 Symbol 

TEST

:   Test mode (Every movement switches on the 

light for a period of 1 second, switching it off for a period 

of 2 seconds after that regardless of the level of brightness.)

Twilight-switch for light control (relay 1)

The switch-on value for the light can be set at between 10 

and 2000 Lux. Using the rotary control, the luminance set 

points can be set as desired. 
Symbol  : 

Night-time operation

Symbol  :   Daytime/Night-time operation

Orientation lighting

This rotary controller serves to determine the working time 

of the orientation lighting (fixed to 20 %).

“ON” for permanent orientation lighting.  

“OFF” for deactiviation of orientation lighting.

25 22

18

16

10

3

1

TEST

6

30

R1

120 6050

40

30

15

10

A

16 10

5

2

1

30

15

TEST

2000

1200

600

200

40

5

60

5

10

30

50

ON

OFF

Unlocking device

Lock device

Luminance set point for constant light regulation 

Dimming 

The following approach will prove useful when setting a 

command value (example workplace): Place a luxmeter flat 

on the desk, then, using the remote control IR-PDim, adjust 

the light up or down by pressing the keys max or min until 

the desired command value which best suits your require-

ments has been reached.

Automatic reading in the current light value  

as new luminance set point

Individual light value 2 - 2500 Lux

Follow-up time 

1 up to 30 min.

Orientation lighting and its follow-up time
OFF button: 

No orientation light.

Grey button:

  Programming the switch-off delay time.

On button:

    Orientation light is permanently activated.

Note:

 During the orientation light phase, the constant light 

regulation is also active: if there is sufficient brightness,  

dimming occurs < 2 V and, if applicable, the lighting is 

switched off.

Preset/user mode => (see page 2, point 6)

Fully automatic/semi automatic mode => (see page 2, point 5)

Semi automatic: green LED,  

Fully automatic: red LED on for approx. 3 sec.

Resetting when open

All values which have been programmed using the remote 

control IR-PDim are deleted, and those values which have 

been set by potentiometer are activated.

Lock device

Test mode 

Reset to deactivate

Resetting when closed

The lighting relay is switched off, i.e.  

opened and the follow-up times reset.

Permanent protection against sabotage

This function blocks the unit permanently (green LED is illuminated). 

This operating mode can only be activated during the period of 5 

seconds after pressing the “lock“ button. This status will only  

permit actuating the function “Light on/Light off”.
The procedure for leaving this mode is as follows:

 

1. Switch off the current

 

2. Apply current for 31 – 59 seconds 

 

3. Switch of the current again 

 

4. Apply current 

 

5. Open detector

Light on/off

The light will remain switched on/off for as long as movements 

are detected in the areas of coverage. Once the last movement  

has been detected, the light will remain on for the duration of the 

follow-up time as per setting.  

The appliance will then return independently to the mode selected 

(Fully or Semi-automatic).

Option:

Wall bracket for remote  

control IR-PDim

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

20 %

max

50

Lux

1500

Lux

ON

OFF