Sensor and power supply in one case for onwall-, ceiling-
and flushmounting
Power supply:
230 V~ +6 %/-10 %
Power consumption:
< 1W
Ambient temperature:
-25°C to +50°C
Degree of protection /class:
SM IP54, FC and FM IP20, FC
with accessory IP23 / II
Settings:
manually and by remote control
Light values:
50 - 1500 Lux (Remote control)
Extension of the detection area:
with Slaves
Area of coverage:
square 4 x 90°
Range of coverage Ø H 2,50 m / T = 18°C:
seated 4.20 m / tangential 7.50 m / radial 4.50 m
Recommended height for mounting:
2 - 3 m
Light measurement:
mixed light, da artificial light
Lux values:
10 - 2000 Lux (Potentiometer)
• Relay/Channel 1 for light-connection
Type of contact:
dry contact type NO
Contact load:
2300 W cos (
ϕ)
=1 / 1150 VA cos (
ϕ)
= 0.5
DIM-Output:
1 x (1-10 V)
Max. no. of series-connected electronic ballasts:
max. 50 electronic ballasts by one single supply with
max. 100 m cable run and a conductur cross-section of
0.75 mm²
Time-settings:
1 - 30 min. / Test
Dimensions H x Ø [mm]
SM
FC
FM
PD1-M-DIM
80 x 98
103 x 97 84 x 97
Visible portion when built into ceiling:
30 x 97 mm
Technical data PD1-Slave
Electrical data same as above, but just one channel for
signaling motion detection.
Declaration of Conformity:
The product complies with
the low voltage recommendation 2006/95/EC and the
EMV recommendation 2004/108/EC.
12. Technical data PD1-Master-DIM
11. PD1-M-DIM - Connections
Type
SM
FC
FM
PD1-M-DIM (Master)
92179
92176
92173
PD1-S (Slave)
92178
92175
92172
LUXOMAT
®
Remote control:
IR-PDim (incl. wall bracket)
92200
Accessory:
BSK Ball basket guard
92199
Wall bracket for remote control as replacement 92100
Occupancy detectors - Covering IP23
92206
Socket IP54
92161
SM-Socket for PD1-FM
92171
9. Article / Part nr. / Accessory
M
A
N 6
32
0
– 2
11
20
9–
1
8. Range of Coverage
13. LED-functional indicators, fault-finding
The functional indicators in the case of the
LUXOMAT
®
PD1-M-DIM (red and green LED‘s)
Red LED indicating self-checking mode (over a period
of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM/memory empty
Flashing rapidly
EEPROM/memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for
commands from the remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when
an attempt is made to input twilight-value are too
bright or too dark
Green LED as an acknowledgement of receipt for
commands from the remote control
Lights up for 3 seconds
Semi automatic or user signal correctly received
Green LED as an indicator of status (only for status
“Permanent protection against sabotage”
)
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
lluminated for 2 seconds
Signal validly received
(dependent upon operating mode)
1
2
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
Walking across
Walking towards
Seated
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
7.5
0 m
4.20 m
7.50 m
4 x 90°
2.50 m
1
2
Connections PD1-M-DIM
–
+
N
R
–
+
L S
SLAVE
L'
1-10 V
3
3
6. Manual Dimming - Preset / User
(for IR-PDim functions see page 1)
You can dim manually by pressing the pushbutton
for a long time (> 2 sec). When the button is released,
the current dimming value is retained. Upon renewed
dimming, the dimming direction is reversed.
PRESET
–
the luminance set point is set during start-up
operation by the installer and remains unchanged. The
luminance set-point configured through manual dim-
ming is only applied for the time being.
Caution:
The constant light regulation is now deactivated!
The currently set artificial light is retained independent
of the ambient/daylight brightness!
After switching off and then back on, the originally set
luminance set-point is reset = constant light regulation
is activated.
USER
- can only be activated via the remote control!
The luminance set-point is changed upon each manual
dimming and re-adjusted by the user (Conformation
through relay clicking!).
The constant light regulation remains activated!
5. Fully / Semi automatic mode
(for IR-PDim functions see page 1)
Fully automatic operation
In this operating mode, the lighting switches automati-
cally on and off for increased comfort, depending on
presence and brightness.
Semiautomatic operation
(Semiautomatic can only be activated via the remote
control!)
In this operating condition, in order to gain increased
savings, the lighting is energized only after being manu-
ally switched on. Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switching-
on must always be carried out manually!
As many (closer-contact) buttons as desired can be wired
in parallel on the “S” button input (ON/OFF Dimm).
7. Manual Switching
You can switch the lighting on and off manually by
pressing the pushbutton for a short time. It will stay
on or off as long as people are detected plus the
configured follow up time.
10. Wiring diagrams
Push button operation
For manual switching
push the button only a short time (0.2 - 0.5 sec.)!
To dim push the button until the wished light level is
arrived.
Master-/Slave-operation. The Master is the only one
to read the light level and to switch the connected
loads. Independant of the light level the Slave units
react to movements only by sending impulsions via
the dry contact.
No load can be connected to the dry con-
tact. The Master-dim-occupancy detectors
can not be switched into parallel. For that
application please prefer the Master-/
Slave-installation. It is recommended to put
the Master the furthest possible postion
away from the natural light source.
1-10
VDC
Terminal connection for push button operation
MASTER
+
R L' N L S
1-10 VDC
Terminal connection for Master-/Slave-operation
MASTER
SLAVE
R R N N L L
R
L' N L S + -