  1. Product information

• 

Extremely slim design with spring clips for easy and  

time-saving installation directly in suspended ceilings

• 

Remote controllable occupancy detector 

LUXOMAT

®

  

PD11-M-1C-FLAT-FC  for indoor applications in the version 

master with circular detection area

• 

One switching channel for switching light

• 

Configuration and operation with the optional remote 

control possible 

LUXOMAT

® 

IR-PD-1C (Accessories)

• 

Version as Master/Slave

2. Operation

The presence detector controls the light automatically according 

to people present (movements) and the ambient brightness.
The integrated light sensor constantly measures the ambient light  

and compares it with the brightness level on the detector. If the 

ambient light is sufficient, lighting will not be switched on.  

If the ambient light level is below the brightness level, a move-

ment activates the lighting in the room.
The detector switch the light off, if there is enough natural light 

for 15 min. or until the follow-up time do not recognized any 

movement in the room.

3. Safety information

!

   Work on the 230 V mains supply may only be car-

ried out by qualified professionals or by instructed 

persons under the direction and supervision of quali-

fied skilled electrical personnel in accordance with 

electrotechnical regulations.

!

  Disconnect supply before installing!

 

!

   This device is not suitable for disconnection.

4.   Mounting

A circular opening of diameter 44 mm must be produced in the 

ceiling. 

 Having connected up the 

cables in accor dance with 

regulations, the detector is 

inserted into the opening 

as shown in the drawing 

opposite and fixed into 

position with the assistance 

of the spring clips.

For mounting into luminaires 

use the supplied clamp ring 

and remove the spring clips.

!

    

In Master-/Slave-operation the master device must  

always be installed at location with least daylight.

5.  Position LEDs

I

II

III

LED I red

LED II white

LED III green

6. Self test cycle/Startup behavior

The product enters an initial 60-second self-test cycle, when the  

supply is first connected. During this time the device does not 

respond to movement and stays on. 

The initialization mode can be changed by using the remote 

control.

After the self-test cycle (60s), the detector is ready for operation.  

There are no further settings necessary. The factory settings 

of brightness threshold and delay time are explained in the 

technical data.

7. Wiring diagram

Standard mode with Master/Slave

N

L

N S R

L‘ L

T1

N

L

R

Slave

Master

!

  Connected slaves must have the same phase as the master.

8. Range

2

1

1

quer zum Melder gehen 
frontal zum Melder gehen
Unterkriechschutz

Walking across

2

quer zum Melder gehen 
frontal zum Melder gehen
Unterkriechschutz

Walking towards

quer zum Melder gehen 
frontal zum Melder gehen
Unterkriechschutz

Seated

9 m

6 m

3 m

9 m

360°

2,50 m

9. Exclude sources of interference

If the detection zone is too large, or areas covered that should not 

be monitored, use the blinds to reduced or limited those areas.

10. Technical data

Power supply:

   

110-240 VAC, 50/60 Hz 

Power consumption:

  

ca. 0.35 W

Ambient temperature:

 

-25°C – +50°C

Degree of protection/class:

   IP20 / II 

Switching power /  

contact: 

2300 W cos

ϕ

=1  

 

1150 VA cos

ϕ

= 0.5, µ-Contact 

Factory reset: 

500 Lux, 10 min.

Recommended height  

for mounting:

  

2 - 3 m

Range of coverage Ø  

H 2,50 m / T = 18°C:

 

seated 3 m / tangential 9 m /  

 

radial 6 m

Area of coverage:

  

circular 360°

Brightness threshold:

 

10 - 2000 Lux

Follow-up time:

 

5 - 30 min.

Settings can be changed by using the optional remote control

Dimensions:

 

H 60 x Ø 52 mm

Technical data PD11-Slave

Power supply:

  

110-240 VAC, 50/60 Hz

Impulse output:

   

Optocoupler max. 2 W

Impulse duration:

     

9 s

 

Declaration of Conformity:  

This product respects the directives concerning

1.   electromagnetic compatibility (2004/108/EU)

2.  low voltage (2006/95/EU)

3.   restriction of the use of certain hazardous substances in electri-

cal and electronic equipment (2011/65/EU)

WE RECOMMEND LIGHTS SHOULD HAVE A 100HR BURN IN (T5 

TUBES OR 80HR FOR T8 TUBES) BEFORE DIMMING OPERATION 

TAKE PLACE.  
THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN 

DOES NOT TAKE PLACE.

11. Article / Part nr. / Accessory

Articel

FC

PD11-M-1C-FLAT-FC

92583

PD11-S

92593

LUXOMAT

®

 Remote control:

IR-PD-1C (incl. wall bracket)                                  92094 

IR-PD-Mini 

                                       92159

12. Manual switching

S-terminal:

By pressing the pushbutton, the phase can be given to the S

terminal.

To turn on or off, press the light briefly. The light will remain on

or off, as people are detected plus the follow-up time.

R-terminal:

The R terminal is used for connecting the slave to the master. 

Alternatively, the phase can be set by a switch on the R terminal. 

If the phase is longer then 10 sec. on, the detector switches to 

permanent mode, as long as the pushbutton is closed.

13. LED-functional indicators

LED function indicators after each mains recovery (60sec. 

initialisation period)
Operating state

LED function indicators

Factory pro-

gram active

White, red and green flash in quick 

succession for 10 sec., then initialisation 

indicators, see below

Indicator  

unprogrammed

Standard 

mode

Red flashes

LED function indicators during operation

Process

LED function indicators

Motion detection

Red flashes on each detec-

ted movement

Too bright detected

Green flashes

Light measurement active

Green flashes once every 

10 sec.

44 mm

PD11_NEU_4lang_211014.indd   1

04.12.2014   15:31:03