background image

14.  Putting into operation of the remote control  

IR-PD-1C (optional)

Remote control LUXOMAT

®

 IR-PD-1C

      Check Battery:

 Open battery compartment 

by pressing the plastic springs together and 

removing the battery-holder.

LUXOMAT

®  

 

PD3

B.E.G.

500

200

400

100

20

IR-PD-1C

PIR

CdS

ON/OFF

HA

B.E.G.

LUXOMAT

®

B.E.G.

LUXOMAT

®

IR-PD-1C

 

Wall bracket for  

remote control IR-PD-1C 

15.  Settings by remote control when open

Unlocking device 

– Activation of the 

programming mode

Locking device - Exit 

programming mode 

If there is not reaction 

for about 3 minutes 

the programming 

mode will be deac-

tivated.

Change between 

fully automatic and 

semi automatic 

mode (HA)

Luminance set 

point 20 - 1000 Lux

Automatic reading 

in the current light 

value as new lumi-

nance set point

Change between 

motion detector 

and photo electric 

switch

Increase the cur-

rent light level by 

20 resp 50 Lux

Light ON/OFF

HA

ON/OFF

Resetting 

when open: 

Deletes 

all values 

set with 

the remote 

control, light 

OFF.

 

or

1000

20

at

+

Follow-up time 

Channel 1 

5 - 30 min. or  
impuls 

��

���

 

LED ON/OFF (by 

holding down the 

push button)

or

Detection sensitivity 

reduced or normal

��

���

at

��

���

min

Daytime operation, 

detector only acti-

vated by motion

or

PI R

CdS

Permanent protection 

against sabotage

White LED flashes

w

hen c

hoo

sing CdS

optional

optional

optional

optional

optional

optional

t < 5 s

16.  Key functions in closed state

    

Light ON/OFF during the detection of motion plus

            follow-up time; Activation of the 12 h-ON/OFF-function 

by holding down the push button

   Activation/Deactivation of the test function

      Switches channel off and is immediately active again,

            exits all timers, interruption of light measurement

    Changes to “open“ state

17.   Explanation of the remote control button  

functions

       17a.  In the initialisation period/during self-test cycle

   Turn off or turn on the detector during the self-test cycle of 

60 sec. The final state is active. Factory settings of the light 

is on during initialization.

    

!

    Initialization mode INI-OFF the detector does not  

turn on after the power supply voltage. A movement 

switch on the detector after 60 seconds.

  

12 h Light ON/OFF (party function)

 

 Activated by “Light“ - push button 

 Deactivated by “Reset“- push button (default) 

  Corridor function 

          

Activated by “outside“- push button

         Deactivate by “inside“- push button (default))

   Forced shutdown

 

 Activated by “sun“ - push button

         Deactivate by “moon“- push button (default)

         17b. In opened state

  This push button opens the detector and the following  

 functions  can then be programmed. 

 

Attention: 

The detector is closed automatically: 

 • after every voltage recovery 

 • after 3 minutes

  The state changes to “closed“. In the first 5 seconds, the white 

LED flashes every 0.5 seconds. During this time, sabotage 

protection can be activated.

  

The device distinguishes between 2 procedures: 

• 

Reading in with lighting switched on:

  

The switch-on value is determined automatically.

 

 Determining the switch-on value:  

1. Press the “eye“ push button  

2. Switch off the light (2 seconds later)  

3. Read in the brightness 

4. Switch-on value = Read brightness  

 

 • 

Reading in with lighting switched on:

  

When the push button is pressed, the current brightness 

is specified as the switch-on value. The switch-off value is 

determined automatically. 

1000

20

   If the brightness has been modified, the switch-off threshold 

is recalculated.

+

   Each time the push button is pressed, the device increases 

the current switch-on value in increments of 20 lux for a 

current switch-on value of < 100 lux and in increments of 

50 lux for a current switch-on value of > 100 lux.

 

  Standard sensitivity for most applications

        Reduced sensitivity for outdoor applications

When the pulse function is active, a pulse of 1sec. is 

generated every 9 sec. If the pulse function is activated via 

remote control, the pause between 2 pulses can be modi-

fied. After activating the function via the “Pulse“  

push button, select the desired time within 5 sec.: 

��

���

min

= 9sec., 

��

���

10 

min

= 10sec., 

��

���

15 

min

= 15sec., 

��

���

30 

min

= 30sec.

PD11_NEU_4lang_211014.indd   2

04.12.2014   15:31:04

Reviews: