14. Putting into operation of the remote control
IR-PD-1C (optional)
Remote control LUXOMAT
®
IR-PD-1C
Check Battery:
Open battery compartment
by pressing the plastic springs together and
removing the battery-holder.
LUXOMAT
®
PD3
B.E.G.
500
200
400
100
20
IR-PD-1C
PIR
CdS
ON/OFF
HA
B.E.G.
LUXOMAT
®
B.E.G.
LUXOMAT
®
IR-PD-1C
Wall bracket for
remote control IR-PD-1C
15. Settings by remote control when open
Unlocking device
– Activation of the
programming mode
Locking device - Exit
programming mode
If there is not reaction
for about 3 minutes
the programming
mode will be deac-
tivated.
Change between
fully automatic and
semi automatic
mode (HA)
Luminance set
point 20 - 1000 Lux
Automatic reading
in the current light
value as new lumi-
nance set point
Change between
motion detector
and photo electric
switch
Increase the cur-
rent light level by
20 resp 50 Lux
Light ON/OFF
HA
ON/OFF
Resetting
when open:
Deletes
all values
set with
the remote
control, light
OFF.
or
1000
20
at
+
Follow-up time
Channel 1
5 - 30 min. or
impuls
��
���
LED ON/OFF (by
holding down the
push button)
or
Detection sensitivity
reduced or normal
��
���
at
��
���
5
min
Daytime operation,
detector only acti-
vated by motion
or
PI R
CdS
Permanent protection
against sabotage
White LED flashes
w
hen c
hoo
sing CdS
optional
optional
optional
optional
optional
optional
t < 5 s
16. Key functions in closed state
Light ON/OFF during the detection of motion plus
follow-up time; Activation of the 12 h-ON/OFF-function
by holding down the push button
Activation/Deactivation of the test function
Switches channel off and is immediately active again,
exits all timers, interruption of light measurement
Changes to “open“ state
17. Explanation of the remote control button
functions
17a. In the initialisation period/during self-test cycle
Turn off or turn on the detector during the self-test cycle of
60 sec. The final state is active. Factory settings of the light
is on during initialization.
!
Initialization mode INI-OFF the detector does not
turn on after the power supply voltage. A movement
switch on the detector after 60 seconds.
12 h Light ON/OFF (party function)
Activated by “Light“ - push button
Deactivated by “Reset“- push button (default)
Corridor function
Activated by “outside“- push button
Deactivate by “inside“- push button (default))
Forced shutdown
Activated by “sun“ - push button
Deactivate by “moon“- push button (default)
17b. In opened state
This push button opens the detector and the following
functions can then be programmed.
Attention:
The detector is closed automatically:
• after every voltage recovery
• after 3 minutes
The state changes to “closed“. In the first 5 seconds, the white
LED flashes every 0.5 seconds. During this time, sabotage
protection can be activated.
The device distinguishes between 2 procedures:
•
Reading in with lighting switched on:
The switch-on value is determined automatically.
Determining the switch-on value:
1. Press the “eye“ push button
2. Switch off the light (2 seconds later)
3. Read in the brightness
4. Switch-on value = Read brightness
•
Reading in with lighting switched on:
When the push button is pressed, the current brightness
is specified as the switch-on value. The switch-off value is
determined automatically.
1000
20
If the brightness has been modified, the switch-off threshold
is recalculated.
+
Each time the push button is pressed, the device increases
the current switch-on value in increments of 20 lux for a
current switch-on value of < 100 lux and in increments of
50 lux for a current switch-on value of > 100 lux.
Standard sensitivity for most applications
Reduced sensitivity for outdoor applications
When the pulse function is active, a pulse of 1sec. is
generated every 9 sec. If the pulse function is activated via
remote control, the pause between 2 pulses can be modi-
fied. After activating the function via the “Pulse“
push button, select the desired time within 5 sec.:
��
���
5
min
= 9sec.,
��
���
10
min
= 10sec.,
��
���
15
min
= 15sec.,
��
���
30
min
= 30sec.
PD11_NEU_4lang_211014.indd 2