background image

M

A

N 8

19

–2

11

01

4_

PD

11

-M-

1C

-F

LA

T_

EN

_1

21. Reset of the detector

If the permanent sabotage protection is activated,  

the detector can be released again as follows:

• 

Switch off the power supply and switch it back on

• 

Let the sensor to initialize for 31 to 59 secs.  

• 

Switch off the power supply again

• 

Apply power again and wait for for the self testing

• 

Press the unlock

Pushing the „RESET“ button on the remote control, in opened mode, 

will delete all of the values which was set by the remote control 

(beside of INI ON/OFF) and set the detector back to  

it‘s factory reset (500 lux, 10 min.).

18.    Switch-off threshold brightness

1.

   If the switch-on threshold has been modified by the potenti-

ometer or remote control, the switch-off threshold stored in 

the EEPROM is deleted and is then recalculated on the next 

activation.  

Determining the switch-off value 

1. Switch on for 5 min. with dark and motion 

2. Light OFF for 2 sec. 

3. Internal calculation of the switch-off value 

2.

  If the eye push button is pressed, the switch-off threshold is  

recalculated. See also Remote control –> Eye section 

3.  

Switch-off delay 

If the determined switch-off threshold is exceeded during 

operation, the detector only switches off after a delay of ap-

prox. 15 minutes. This compensates for any brief fluctuations 

in the brightness.

19a.  Behaviour of external push button/ 

IR “Light“ 

The “Corridor“ and “Light ON/OFF“ functions are mutually 

exclusive. If both are activated, the detector performs the cor-

ridor function.
The behaviour when the push button is pressed is defined as 

follows:

Corridor function activated

Light ON:

 

Push button pressed briefly: Light OFF -> Active after 5 sec.  

Push button held down: Light OFF -> Active after 5 sec.

Light OFF:

 

Push button pressed briefly: Light ON as long as Lag 

time 

Push button held down: Light ON as long as Lag time

Party function 12 h Light ON/OFF activated

Light ON:

 

Push button pressed briefly: Light OFF -> Active after 5 sec.  

Push button held down: 12 h OFF

Light OFF:

 

Push button pressed briefly: Light ON as long as Lag time 

Push button held down: 12 h ON

Corridor- und Party function 12 h Light ON/OFF deactivated

Light ON:

 

Push button pressed briefly: Light OFF as long as Lag time 

Push button held down: Light OFF as long as Lag time

Light OFF:

 

Push button pressed briefly: Light ON as long as Lag time 

Push button held down: Light ON as long as Lag time

19b.  

 Behaviour of external push button/IR  

“Forced shutdown“

Forced shutdown active 

 

Light OFF:

 

Light OFF: Push button pressed briefly: Light ON for approx. 

30 min., then forced shutdown if the set brightness is still 

exceeded.

20.  

Fully automatic and semi automatic mode

 

HA

ON/OFF

 

(see functions IR-PD-1C)

 

Fully automatic operation

In this operating mode, the lighting switches automatically on 

and off for increased comfort, depending on presence and 

brightness.

- Channel 1 switches on in the event of motion if “dark“ is 

detected.

Semi automatic operation

In this operating condition, in order to gain increased  

savings, the lighting is energized only after being  

manually switched on.

Switch-off takes place automatically or manually.

The semi automatic mode basically behaves like the fully 

automatic one. However, the difference is that switching-on must 

always be carried out manually!

As many (closer-contact) buttons as desired can be wired in 

parallel on the “S” button input (ON/OFF).

Triggering in semi automatic mode: 

If the detector switches 

off in semi automatic mode (lag timer elapsed), the detector 

is switched on again within 10 sec. by motion (despite semi 

automatic mode).

LED function indicators after each mains recovery  

(60sec. initialisation period)
Operating 

state

LED function indicators

Factory pro-

gram active

White, red and green flash in quick 

succession for 10 sec., then initialisation 

indicators, see below

Indicator  

unpro-

grammed

Indicator  

program-

med

Indicator also 

when forced shut-

down is activated

Standard  

mode

red flashes 

quickly

Every 5 sec., 4 

x white, red and 

green in quick 

succession

12 h ON/

OFF active

Red and 

green 

flash

Red and 

green 

flash 

quickly

Every 5 sec., 4 

x white, red and 

green in quick 

succession

Corridor  

active

Red and 

white 

flash

Red and 

white 

flash  

quickly

Every 5 sec., 4 

x white, red and 

green in quick 

succession

12 h ON/

OFF & corri-

dor active

Red, green 

and white 

flash

Red, 

green 

and white 

flash 

quickly

Every 5 sec., 4 

x white, red and 

green in quick 

succession

CdS 

active

Red and 

white 

flash

Then no red 

LED for motion 

detection

LED function indicators during operation

Process

LED function indicators

Semi-automatic mode active

White is ON

Corridor active

White ON 1 sec. and OFF 

4 sec. aus

Corridor and semi-automatic 

mode active

White ON 4 sec. and OFF 

1 sec.

12 h ON/OFF function active Red and green flash 

alternately

IR command

White flashes once

IR-command „Open“ and 

Sabotage active

white and green

flashes once

Permanent on/off

red flashes

22. 

LED-functional indicators remote control