Installation and Operating Instruction for
B.E.G.
- Occupancy detectors PD2-M-2C-24V-3A-SM/-FC and PD2-M-2C-24V-RR-SM/-FC
2a. Installation of the LUXOMAT
®
PD2-M-2C-24V-SM
The detector must be installed on a solid
and level surface. There is no need for
frames.
For mounting remove lens (C) (turn
anticlockwise). Fasten the mounting pod
to the ceiling.
Having connected up the wires in accord-
ance with regulations, secure the detector
with 2 screws as per the illustration above.
In order to assemble the detector outside, the PD2-IP54 base-plate,
which is available as an accessory, must be mounted between the
detector and the surface on which it is to be installed.
LUXOMAT
®
PD2-M-2C-24V
2b. Installation of the LUXOMAT
®
PD2-M-2C-24V-FC
The detector has been designed
and developed specifically for in-
stallation in suspended ceilings.
A circular opening of diameter
68 – 70 mm must be produced in
the ceiling.
Having connected up the cables
in accor dance with regulations,
the detector is inserted into
the opening as shown in the
drawing opposite and fixed into
position with the assistance of
the spring clips.
The product enters an initial 60-second
self-test cycle, when the supply is first
connected. The occupancy detector is
ready for operation.
2c. Self test cycle
3. Putting into operation / Settings
Follow-up time for light control
The time can be set infinitely variably at between
15 seconds and 16 minutes.
Symbol : impulse < 1sec.
Symbol
TEST
: Test mode
(Every movement switches on the light for a period of 1
second, switching it off for a period of 2 seconds after
that regardless of the level of brightness.)
Twilight-switch
The switch-on value for the light can be set at between
10 and 2000 Lux. Using the rotary control, the luminance
set points can be set as desired.
Symbol : Night-time operation
Symbol : Daytime/Night-time operation
Follow-up time for appliance-control
The time can be set infinitely variably at between
5 minutes and 120 minutes. There is a period of delay
prior to switch-on of between 5 - 10 minutes for times set
in excess of 15 minutes.
Symbol
: Impulse = 1sec.
Symbol
A
: Alarm impulse = 1sec.
Option:
Wall bracket for remote
control IR-PD
IR-PD
IR-PD-Mini
1. Mounting preparations
Work on the 230 V mains supply
may only be carried out by qualified
professionals or by instructed persons
under the direction and supervision
of qualified skilled electrical person-
nel in accordance with electrotechni-
cal regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
4. Settings carried out using remote control (optional)
Remote control LUXOMAT
®
IR-PD
1. Check Battery:
open battery compartment by pressing the
plastic springs together and removing the
battery-holder.
2. IMPORTANT
Please pay attention, that the setting is Potentio-
meter 1 at “TEST” and Potentiometer 2
not
at
“SUN”. All values which have been programmed
using the remote control will be deleted in the
event of power failure in the position “TEST/
SUN”. Please switch Potentiometer 2 over to
“MOON” or any other value.
Caution:
Settings with remote control supersede the
settings by courtesy of potentiometers.
max
50
Lux
1500
Lux
ON
OFF
Lock device
Test mode
Reset to deactivate
Resetting when closed
The lighting relay is switched off, i.e.
opened and the follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is
illuminated). This operating mode can only be activated
during the period of 5 seconds after pressing the “lock“
button. This status will only permit actuating the function
“Light on/Light off”.
The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 – 59 seconds
3. Switch of the current again
4. Apply current
5. Open detector
Light on/off => (see page 2, point 6)
The light will remain switched on/off for as long as move-
ments are detected in the areas of coverage. Once the last
movement has been detected, the light will remain on for
the duration of the follow-up time as per setting.
The appliance will then return independently to the mode
selected (Fully or Semi-automatic).
Unlocking device
Lock device
Luminance set point
Automatic reading in the current light value
as new luminance set point
Individual light value 2 - 2500 Lux
Follow-up time (relay and channel 1)
15 sec. up to 30 min.
Impulse function (relay and channel 1)
1sec. ON, 9 sec. OFF
Time setting (relay and channel 2)
5 min. up to 120 min.
Impulse function (relay and channel 2)
The voltage-free contact is closed for a period of 2 seconds.
This is followed by a period of idle time of 8 seconds’ duration.
Alarm impulse program for appliance control (relay 2)
The relay will not close until at least three movements have been
registered over a period of 10 seconds (impulse = 1 second).
Preset/user mode
Fully automatic/semi automatic mode => (see page 2, point 5)
Semi automatic: red LED (flashing),
Fully automatic: red LED on for approx. 3 sec.
Resetting when open
All values which have been programmed using the remote
control IR-PD are deleted, and those values which have
been set by potentiometer are activated.
��
���
A
3
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
����
���
��
���
��
���
R1
�
���
���
���
R2
120 6050
40
30
15
10
A
16 10
5
2
1
30
15
TEST
2000
1200
600
200
40
5
120 6050
40
30
15
10
A
16 10
5
2
1
30
15
TEST
2000
1200
600
200
40
5
120 6050
40
30
15
10
A
16 10
5
2
1
30
15
TEST
2000
1200
600
200
40
5
GB