background image

USA-EN

Installation and Operating Instruction for 

B.E.G.

 Controls - Occupancy sensor MINI-P-PP-A-GH-FC

MINI-P-PP-A-GH-FC

Controls

B.E.G.

 34 mm

≤1.3 in

RJ12

1

  1. Product information

• 

MINI high bay primary sensor for use with PP-

A-J and PP-1-J power packs or proprietary low 

voltage system

• 

Designed for indoor locations - High Ceilings

• 

Up to 4 Secondary sensors may be connected 

with a primary sensor to increase detection 

coverage.

• 

Spring clips for quick and easy installation in 

suspended ceilings and light fixtures

• 

5-year limited warranty

• 

Masking blinds included

• 

All programmable features can be adjusted via 

B.E.G. Controls smartphone IR-Adapter and 

Android or iOS app.

• 

ROHS compliant

• 

Photocell included as a standard feature

2. Operation with power pack  

  PP-A-J and PP-1-J

The MINI with B.E.G. PP-A power pack detects 

both motion and the ambient light level in the 

room and then automates the lights according to 

the parameters set by the installer and/or building 

management. The integrated light sensor constantly 

measures the ambient light and if the light level is 

sufficient, the light will be switched off. If the ambient 

light level is below the preset brightness level the 

lights will be allowed to come on when the sensor 

detects movement in the room.
When motion is detected in the room, the PP-A‘s 

auxillary dry contact relay will send a signal to HVAC 

or other systems indicating that the room is occupied. 

With the integration of simple off the shelf, normally- 

open momentary switches, the MINI-PP-A can be set to 

operate in vacancy mode via the auto/manual switch 

selector on the power pack. The switches can be used 

to turn off the lighting before the preset time out period.

3. Safety information

!

  

 Work should be carried out by qualified pro-

fessionals or by instructed persons under the 

direction and supervision of qualified skilled 

electrical personnel in accordance with electri-

cal regulations.

!

   The device is not to be used to isolate other 

equipment from the mains supply!

4.   Mounting

Select sensor(s) mount-

ing location based on 

room dimensions and 

sensor coverage pattern. 

Avoid placing sensor(s) 

less than four feet away 

from  heat and/or ven-

tilation sources. Avoid 

placing sensor(s) where 

view will be directed 

outside of intended 

controlled space, this to prevent outside sources from 

activating sensor(s).

A circular opening 1.3 in/34 mm in diameter must be 

made in the ceiling.

Having connected the cables in accordance with the 

national and local electrical codes, connect the sensor 

to the power pack using the RJ12 connector. Pass sen-

sor’s RJ12 connector through ceiling opening. Next, 

squeeze spring clips through ceiling opening. Sensor 

should clip securely into place. (See Figure)

!

    

When using primary and secondary devices, 

please mount the primary device at the place 

with the least amount of natural light.

5.  Position LEDs

LED 1 green/red 

6. Self test cycle/Startup behavior

When power is first applied, the sensor enters an 

initial 60 second self-test cycle. During this time the 

device does not respond to movement and stays on.

7. Range

20ft / 6

m

30 ft / 

9 m

1

1

Walking across

8. Exclude sources of interference

 

To prevent false activation from external heat-emitt 

sources, use blinds to mask sensor viewing angle.

9. Decription / Part No. / Accessory

Description

Part No.

MINI-P-PP-A-GH-FC

97184

MINI-S-PP-GH-FC

97187

Remote control:

via B.E.G. Controls IR-Adapter

92726

Power pack PP-A-J

97020

Power pack PP-1-J

97036

The required app for smartphones can be down-

loaded from the App Store for iOS smartphones and 

Google Play Store for Android smartphones. 

The manual for the B.E.G. Controls App can be 

downloaded from www.begcontrols.com

Note:

  Remote only works with primary MINI-P-PP-A-

GH-FC sensor.

Note:

  Maximum distance between sensor and 

remote - 24 ft/ 7.3 m

10. Technical data

Operating voltage:

      24 V DC 

Ambient temperature:

  -13°F-122°F/-25°C to +50°C

Protection:

  Suitable for indoor use and dry locations 

only.

Factory settings: 

50 fc/500 Lux, 10 min.

Note:

 Maximum mounting height for feasible day-

light control 16.4 ft./5 m.

Natural daylight contribution must be 2.5 times 

the artificial light contribution at the sensor for the 

controlled load to turn-off.

Recommended height  

for mounting:

  

30 ft / 9 m

Range of coverage Ø:

  walking across 19.7 ft /6 m

Area of coverage:

  

360°

Following settings can only be changed using the 

B.E.G. Controls IR-Adapter for smartphones and app. 

Brightness threshold:

  2 - 100 fc/20 - 1000 Lux 

Follow-up time:

 

 Load: 30 sec. - 30 min. 

HVAC: 5 min. - 120 min.

Sensitivity: 

MIN-LOW-MID-HIGH-MAX

Dimensions:

 

 H 1.93 in x Ø 1.77 in  

H 49 x Ø 45 mm

Technical data MINI-Secondary

Operating voltage:

    24 V DC

Pulse output:

   

Digital output

    

11. Manual switching

!

  

See manual of the power pack PP-A/PP-1: “PB 

load” and “All off” (only PP-A)!

12. LED-functional indicators

LED function indicators

Process

Red blinks once per 

second during the 

first 60 seconds after 

powering

Self-test cycle, unmodified 

device

Red blinks twice per 

second during the 

first 60 seconds after 

powering

Self-test cycle, previously 

modified device

Red flashes

Motion detected

Green blinks once per 

second

Too bright detected

Red and green  

flash once in quick 

succession

Remote control signal 

received

Red and green blink 

together once every 4 

seconds

Device operates in pulse 

mode 

Green is on for 4 

seconds

Remote control signal 

received  but device is 

locked

Green flashes twice per 

second for 5 seconds

Device has just been 

locked and can now be 

double locked

 

Summary of Contents for MINI-P-PP-A-GH-FC

Page 1: ...eze spring clips through ceiling opening Sensor should clip securely into place See Figure When using primary and secondary devices please mount the primary device at the place with the least amount of natural light 5 Position LEDs LED 1 green red 6 Self test cycle Startup behavior When power is first applied the sensor enters an initial 60 second self test cycle During this time the device does n...

Page 2: ...to power pack and wait for the sensor to go through self testing Press the unlock button Pressing the RESET button on the remote control in programming open mode will delete all of the values set by the remote control Sensor settings will be set back to factory settings 50 fc 500 Lux 10 minute timeout B E G Controls 277 Highway 74 N Suite 319 Peachtree City GA 30269 Phone 770 349 6341 Email info b...

Page 3: ...ed in correctly Step 4 Please check that the Smartphone s loudness level is maximum in order to ensure a correct operation 2 Procedure to use the remote control app Start page Help To access the device selection page click on the three white horizontal lines in the upper left corner or swipe from left to right Device or remote control selection Select Remote controls Select IR MINI P Functions Dev...

Page 4: ...and send 3 Send multiple parameters at once You may want to apply the same parameter settings to more than just one MINI Primary sensor in this case you can use the Activate Deactivate function to select multiple commands The Send highlighted commands button will then send all selected parameters Please note that this is only applicable for open state functions The app will always send the Open de...

Reviews: