**Error detection off by default (can be activated via NFC app or LORA downlink)
10. Battery and replacement procedures
The thermal energy meter constantly monitors the status of the battery (
maximum life: 10 years*
) and signals the imminent discharge by
showing the icon on display
. Reporting takes place one year before full discharge. For replacement, contact the manufacturer
.
*The battery life strongly depends on the working time window, set during the configuration process,
and on the environmental conditions. Estimation of the battery life is given by the configuration
software.
The thermal energy meter uses non-rechargeable batteries that, if misused, can be potentially dangerous.
To reduce the risks, you should take the following precautions:
Do not recharge or replace the battery;
Do not open, puncture or damage the batteries;
Do not short-circuit the battery;
Do not expose the battery to temperatures above 85° C;
Do not insert into ovens, crush or cut: these actions could cause an explosion or leakage of flammable gases or liquids.
Do not use naked flames near the device;
Do not put in contact with water;
Do not expose the battery to an extremely low pressure environment which could cause an explosion, a gas or flammable liquids leak;
Always dispose of batteries in compliance with current regulations;
Always use original spare parts authorized by the manufacturer;
24**
Excessive temperature
The error occurs when ambient temperature higher than +80 °C is detected.
25
Display Overflow
The error is triggered when the energy digits, based on the selected unit, go beyond
what is allowed.
26-27
Reserved
Please contact your dealer
28**
No consumption C1
The error is activating when no pulses are detected for 7 consecutive days on the C1
pulse input.
29**
No consumption C2
The error is activating when no pulses are detected for 7 consecutive days on the C2
pulse input.
30**
Loss on C1
The device detects continuous pulses on C1 for 12 hours.
31**
Loss on C2
The device detects continuous pulses on C2 for 12 hours.
32**
Too frequent pulses C1
The error is triggered when too frequent pulses are detected on C1.
33**
Too frequent pulses C2
The error is triggered when too frequent pulses are detected on C2.
34**
Too frequent MBUS readings
The error is triggered when too many MBUS queries are made under the minimum
limit of 15 minutes.
35
MBUS disconnected
The error is triggered when MBUS communication is not detected for 2 consecutive
hours.
36
Wrong module
The error is triggered when the external module has been removed and a second
module is mounted.
37
Module Removal
The error is triggered when the module is not detected anymore.
38
End of battery life module
The error is triggered when the remaining battery life of the module is less than 1 year.
39
Module magnetic fraud
The error is triggered when a magnetic field is detected for an extended period of time.
40
NFC Fraud
The error is triggered when an NFC field is detected for more than some minutes.