The consultation menu is divided into 9 levels by a numerical index
always visible at the top left of the display.
By pressing the T1 button you can choose the desired level, while
pressing the T2 button you can view the sublevels of the preset
level.
After 60 seconds without iteration the display turns off. If no button
is pressed within 20 seconds (with the display off) the display cycle
will start again from level 1. If a button is pressed within 20 seconds
(with the display off) the last level consulted will be displayed.
In any level or sublevel, holding down the T1 button for 3 seconds
will direct the index to level 1.
To access to a sublevels, where present (indicate by the symbol ‘–‘),
it is necessary to hold down the T2 button for 3 seconds. To return
to a main level from a sublevel it’s necessary to hold down the T2
button again for 3 seconds.
Each level consists of a brief indication in letters of the data that will
be shown after a few seconds in a second screen. Specifically, the
cycle will be defined as follows:
›
First consultation: 2,5 seconds the indication in letters and 5,5
seconds the data.
›
2-n consultations: 1 second according to the indication in letters
and 6 seconds the data.
Note
: in absence of historical data, levels 6-7-9 will show - -
(text). Below, the navigation map of the consultation menu is shown.
In this level, based on the order, the configuration of the thermal energy meter (installation version and unit of measurement) is already
managed. NFC communication it is disabled in this sleep phase.
Note
: it’s necessary to holding down the T2 button for 3 seconds for the
thermal energy meter initialization.
The device is in sleep mode, waiting for T2 long press.
The device is in sleep mode, waiting for configuration via buttons or NFC.
Meter initialization, level 1 (Cumulative energy heating)
Installation version (return, supply).
Meter initialization, level 1 (Cumulative energy heating)
Units of measurement (1=Joule, 2=MJ, 3=GJ, 4= kWh, 5=Mwh)
Procedure for commissioning
1)
Check that the mounting position of the thermal energy meter
and all electrical wiring are carried out correctly
2)
Check if the device is configured, otherwise set the installation
version and the unit of measurement
3)
Check at level 3 that all configured parameters are correct
(heating and cooling data)
4)
Check that the thermal energy meter, pulse devices, probes etc.
are installed correctly (refer to the specific installation manuals for
each product)
5)
Start the heating/cooling system:
›
Check the consistency of the reported values (energy and
volume)
›
Check in level 2 the instant data
6)
Check for errors
7)
Apply installation seals. Apply installation seals. It’s recommended
to lock the device with a password set through the BMetering NFC
Config android app (downloadable from the Google Play Store).
6. Consultation menu
Displayed data are only for examples.
For more details refer to chapter 5: Commissioning
To configure the device please refer to chapter
5: Commissioning
Level S1 - Initialization
In this level, the configuration of the thermal energy meter is managed through buttons before its installation.
The “not Set” condition remains active only until no other condition has been selected. When the condition is changed (by pressing T1 or
T2) it will no longer appear. Through NFC it is possible to set unit and installation version. If the parameters are not set via NFC, the device
remains in ‘not set’ mode.
Level S2 - Configuration and initialization