19
User Manual v1.4.3
HYDRODIGIT
LORAWAN PAYLOAD EXAMPLE
Here below you can see an example of payload decoding:
Description of the payload:
Field
Format
Byte
Example
byte
Application code
DEC
45
45
Absolute meter counter (size 1 byte LSB)
HEX
XX
2A
Absolute meter counter (size 1 byte)
HEX
XX
2F
Absolute meter counter (size 1 byte)
HEX
XX
00
Absolute meter counter / reverse flow (size 1 byte MSB-nibble for X/Y)
HEX
XY
00
Reverse flow (size 1 byte LSB)
HEX
YY
86
Reverse flow (size 1 byte)
HEX
YY
00
Reverse flow (size 1 byte)
HEX
YY
00
Alarms (bit 0...5)
Diameter (bit 6)
HEX
KK
0A
Medium (bit 7)
Temperature (size 1 byte MSB)
HEX
TT
00
Temperature (size 1 byte LSB)
HEX
TT
CD
45
2A 2F 00
00
86 00 00
0A
00
CD
Application code
45
Absolute meter counter
002F2A -> 12074 liters
Reverse flow
000086 -> 134 liters
Absolute meter counter / reverse flow
00
Alarms
0A è 0000 |1010 so Burst alarm and wrong installation alarm
Diameter
0 (DN15);
Medium
0 (Water);
Temperature
0x00CD = 205, so +20,5°C